Summary of Contents for Siemens Simatic ET 200S 2/4AI RTD ST
Page 1
Preface SIMATIC ET 200S distributed I/O 2/4AI RTD ST analog electronic module (6ES7134-4JB51-0AB0) ______________ Properties ______________ Parameters SIMATIC ______________ Diagnostics ET 200S distributed I/O ______________ 2/4AI RTD ST analog electronic Analog value representation module (6ES7134-4JB51-0AB0) ______________ Connecting Manual 07/2008 A5E01076865-02...
Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Additional support If you have any questions relating to the products described in these operating instructions, and do not find the answers in this document, please contact your local Siemens representative. http://www.siemens.com/automation/partner...
Page 4
Technical Support You can reach technical support for all A&D projects ● using the support request web form: http://www.siemens.com/automation/support-request ● Phone: + 49 180 5050 222 ● Fax: + 49 180 5050 223 For more information about our technical support, refer to our Web site at http://www.siemens.de/automation/service...
Table of contents Preface ..............................3 Properties ..............................7 2/4AI RTD ST analog electronic module (6ES7134-4JB51-0AB0)..........7 Compatibility with the predecessor module .................15 Parameters .............................. 17 Parameters...........................17 Parameter description........................18 Diagnostics .............................. 19 Diagnostics using LED display.....................19 Error types............................20 Analog value representation ........................21 Introduction ..........................21 Analog value representation for measuring range with SIMATIC S7 ..........21 Measuring ranges ........................22...
Page 6
Table of contents 2/4AI RTD ST analog electronic module (6ES7134-4JB51-0AB0) Manual, 07/2008, A5E01076865-02...
Properties 2/4AI RTD ST analog electronic module (6ES7134-4JB51-0AB0) Properties ● 2 inputs (3- and 4-cable connection) / 4 inputs (2-cable connection) for resistance thermometers or resistance measurement ● Input ranges: – Resistance thermometers: Pt100 (α = 0,003851); Ni100 (α = 0,00618); resolution 15 bit + sign –...
Page 8
Properties 1.1 2/4AI RTD ST analog electronic module (6ES7134-4JB51-0AB0) General terminal assignment Note Terminals A4, A8, A3, and A7 are only available on certain terminal modules. 2/4AI RTD ST terminal assignment (6ES7134-4JB51-0AB0) Terminal Assignment Terminal Assignment Notes : Measuring line positive, channel n •...
Page 9
Properties 1.1 2/4AI RTD ST analog electronic module (6ES7134-4JB51-0AB0) Block diagram Figure 1-1 2/4AI RTD ST block diagram 2/4AI RTD ST technical specifications (6ES7134-4JB51-0AB0) Dimensions and weight Width (mm) Weight Approx. 40 g Module-specific data Supports isochronous operation Supports I&M functions Number of inputs 2, with 3- and 4-wire connection 4, with 2-wire connection...
Page 10
Properties 1.1 2/4AI RTD ST analog electronic module (6ES7134-4JB51-0AB0) Permissible potential difference Between M and the central grounding point • 75 VDC / 60 VAC Insulation tested 500 VDC Current consumption From load voltage L+ • Max. 30 mA Power dissipation of the module Typically 0.6 W Status, interrupts, diagnostics Diagnostics function...
Page 11
Properties 1.1 2/4AI RTD ST analog electronic module (6ES7134-4JB51-0AB0) Data for selecting a sensor Input range (rated value)/input resistance Resistance-type sensor • 150 Ω/min. 2 MΩ 300 Ω/min. 2 MΩ 600 Ω/min. 2 MΩ PTC min 2 MΩ Resistance thermometer •...
Page 12
Properties 1.1 2/4AI RTD ST analog electronic module (6ES7134-4JB51-0AB0) Using PTC resistors PTCs are suitable for temperature monitoring and as thermal protective devices for complex drives and transformer windings. ● Select "Two-wire resistor" and "PTC" when configuring: ● Connect the PTC in accordance with the two-wire connection method. ●...
Page 13
Properties 1.1 2/4AI RTD ST analog electronic module (6ES7134-4JB51-0AB0) ● Assignment in the process input image (PII) in the case of SIMATIC S7 ● Assignment in the process input image (PII) in the case of SIMATIC S5 ● Notes on programming NOTICE Only the bits 0+2 or 3+5 are relevant for the purposes of evaluation in the process input image.
Page 14
Properties 1.1 2/4AI RTD ST analog electronic module (6ES7134-4JB51-0AB0) Example The diagram below shows the temperature pattern and the switching points belonging to it. I&M functions The interface modules identified in the table below (as of order number) can be used to read and write I&M data from the module and for the firmware update: Interface module as of order number...
Properties 1.2 Compatibility with the predecessor module Compatibility with the predecessor module Compatible with 2AI RTD ST analog electronic module (6ES7134-4JB50-0AB0) If you configure the 2/4AI RTD ST (6ES7134-4JB51-0AB0) as predecessor module (6ES7134-4JB50-0AB0), then it behaves as if it is compatible. The following technical specifications of the 2/4AI RTD ST (6ES7134-4JB51-0AB0) have changed values: 2/4AI RTD ST technical specifications...
Page 16
Properties 1.2 Compatibility with the predecessor module 2/4AI RTD ST analog electronic module (6ES7134-4JB51-0AB0) Manual, 07/2008, A5E01076865-02...
Parameters 2.2 Parameter description Parameter description Smoothing The individual measured values are smoothed by digital filtering. The smoothing can be adjusted in four steps, in which the smoothing factor k multiplied with cycle time of the electronic module equals the time constant of the smoothing filter. The higher the smoothing the greater the time constant of the filter.
Diagnostics Diagnostics using LED display LED display ① Batch error (red) Status and error displays Event (LED) Cause Remedy No configuration or incorrect Check the parameter module plugged in. No load assignment. Check the load voltage.present There is a voltage. Evaluate the diagnostic message.
Diagnostics 3.2 Error types Error types Analog input module error types Table 3- 1 Error types Fault type Meaning Remedy 10000: Configuration Module cannot use the Correct the configuration (align error parameter for the channel: actual and preset configuration). Inserted module does not Correct the parameter match the one configured.
Analog value representation Introduction Electronic modules with analog outputs With the electronic module with analog inputs, continuously variable signals, such as those occurring in temperature measurement and resistance measurement, can be acquired, evaluated, and converted to digital values for further processing. Analog value representation for measuring range with SIMATIC S7 Analog value representation With the same nominal range, the digitized analog value is the same for input and output...
Analog value representation 4.3 Measuring ranges Analog values The following table shows the representation of the binary analog values and the corresponding decimal and hexadecimal representation of the units of the analog values. The table below shows the 11, 12, 13, 14, and 15 bit resolutions + sign. Each analog value is entered left aligned in the ACCU.
Page 23
Analog value representation 4.3 Measuring ranges Measuring ranges for resistance thermometer Pt 100 standard Table 4- 4 SIMATIC S7 format: Measuring ranges Pt 100 standard in °C Pt 100 Standard in °C Units Range (1 digit = 0.1°C) Decimal hexadecimal >...
Page 24
Analog value representation 4.3 Measuring ranges Measuring ranges for resistance thermometer Ni 100 Standard Table 4- 6 SIMATIC S7 format: Measuring ranges Ni 100 Standard in °C Ni 100 Standard in °C Units Range (1 digit = 0.1°C) Decimal hexadecimal >...
Analog value representation 4.4 Effect on analog value representation 4.4.2 Effect of the value range on the analog input 2AI RTD Standard The response of the electronic modules with analog inputs depends on the part of the value range in which the input values are located. The table below shows this dependency.. Table 4- 10 Response of the analog modules, depending on the location of the analog input value in the range of values Measured value within ...
Connecting Connecting measuring sensors Introduction You can connect resistances as measuring sensors to the analog input module. In this chapter you will find out how to connect the measuring sensors and what to watch for when doing so. Lines for analog signals You should use shielded and twisted-pair lines for the analog signals.
Page 28
Connecting 5.1 Connecting measuring sensors Connection of isolated measuring sensors to analog inputs The isolated measuring sensors are not connected to the local ground potential. They can be floating. The following figure illustrates the connection of isolated measuring sensors to a floating analog input module: ①...
Connecting 5.2 Wiring unused channels on analog input modules Wiring unused channels on analog input modules Rules Pay attention to the following instructions when wiring unused channels: ● "Disable" unused input channels when setting parameters. ● A disabled channel always returns the value 7FFF ●...
Page 30
Connecting 5.3 Using the shield connection 2/4AI RTD ST analog electronic module (6ES7134-4JB51-0AB0) Manual, 07/2008, A5E01076865-02...