Siemens 3US50 Operating Instructions
Siemens 3US50 Operating Instructions

Siemens 3US50 Operating Instructions

Overload relay with phase loss sensitivity

Advertisement

Available languages

Available languages

Quick Links

Overload Relay with
Phase Loss Sensitivity
Operating Instructions
Read and understand these instructions before installing,
operating, or maintaining the equipment.
DANGER
!
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying this device before
working on this device.
CAUTION
Reliable functioning of the equipment is only ensured with
certified components.
Fig. Ia: 3US50: For mounting on contactors 3TS29 / 30 / 31 / 32,
Individual mounting possible with assembly kit 3US1950-8.
Fig. Ib: 3US55: For mounting on contactors 3TF33 / 34,
Individual mounting possible with assembly kit 3US1955-8.
Mounting
Dimension drawings
(dimensions in mm):
1)
Keep distance to earthed parts.
2)
Where 3TS contactors are screwed or snapped onto a standard mounting
rail (35 x 7.5 mm rail to DIN EN 50 022) fixed onto a non-insulating
surface, insulation should be provided between the relay and the
non-insulating surface so as to obtain the air gap specified in UL 508.
3)
For snap-on fastening on standard sectional rail, DIN EN 50 022.
Dimension for square OFF button (stroke 3 mm).
Dimension for round RESET button (stroke 2.5 mm) dimension minus
2.5 mm.
4)
Permissible installed positions: Fig. III
a Overload relay with contactor
b Overload relay for individual mounting
Do not subject to sudden shocks or long-term vibrations.
Connection
Equipment circuit diagram: Fig. V
Permissible cable cross-sections: Fig. IV
In the case of several single-phase loads, the three main circuits must be
connected in series.
Commissioning
Instructions: Fig. VI
➀ Set the scale to the rated current of load.
➁ Reset button (blue)
Push this button before commissioning and after tripping to make relay
ready for operation.
In the as-delivered condition, the auxiliary contact is set to H = Manual
resetting.
To change from H = Manual to A = Automatic, press and turn the button
counter-clockwise from H to A.
➂ Test button (red)
When this button is actuated, the NC contact opens and the NO contact
closes, i.e. a test function for NC and NO contacts (simulation of overload
tripping).
In the "Manual" position, the relay is reset when the blue button is
pressed.
In the „Automatic" position, the relay is reset automatically when the red
button is released.
➃ TRIPPED indication (green)
In the H setting, a green pin protrudes from the front plate to indicate the
TRIPPED condition. In the A setting, this condition is not indicated.
➄ Terminal for contactor coil, A2.
Tripping characteristics: Fig. VII
The characteristics conform to VDE 0165, VDE 0170 / 0171 for
machines with type of protection E Ex e.
A5E01070504A-02
Order No.: 3ZX3012-0US50-0AY0
Fig. II
DIN VDE 0660 part 102, IEC 60947-4-1,
Tripping times are shown for a three-phase load from the cold state
(ambient temperature +20 °C). In the case of hot relays, preloaded with
1 x I
, the tripping times decrease by approx. 25 %.
E
I
: Current setting
E
t
: tripping time in seconds (+ 20 %)
A
➀ Setting range (I = lowest value of current setting I
current setting I
)
E
➁ Type designation / Order No.
Technical data
Main circuit
Rated insulation voltage
Rated operational current
Permissible ambient air temperature
Degree of protection
Auxiliary circuit
Rated operational current:
AC-15 / U
V
24
e
AC-15 / I
A
2
e
DC-13 / U
V
24
e
DC-13 / I
A
2
e
Rated insulation voltage:
400 V
different potential
Short-circuit protection:
NH, NEOZED or DIAZED fuses
Miniature circuit-breaker
Operating conditions at ambient temperatures > 55 °C
At ambient temperatures > 55 °C, you must
1. Reduce the current loading for the overload relay
2. Upwardly correct the setting current to prevent tripping at motor rated
current.
Correction factors:
Ambient
Perm. Current loading
temperature
referred to end-of-scale value
55 °C
60 °C
65 °C
70 °C
Calculation example:
Motor rated current: 10 A
Ambient temperature: 70 °C
Overload relay fitted: 8 to 12.5 A
1st Step: Determine the permissible current loading:
Max. current loading: 12.5 A x 0.82 = 10.25 A
Loading with motor rated current 10 A at 70 °C ambient temperature is per-
missible.
2nd Step: Calculate the setting current:
Motor rated current: 10 A
Setting current correction: 10 A x 1.1 = 11 A
You must set the overload relay to 11 A.
For further information and accessories, see Catalog IC15.
3US50, 3US55
Q/320500 SMS 011, GB14048.4
English
, II = highest value of
E
690 V
3US50: 0.1 ... 18 A
3US55: 6.3 ... 32 A
-25 °C .... +55 °C
see nameplate
60
125
230
400
500
1.5
1.25
1.15
1.1
1
60
110
220
0.5
0.3
0.2
690 V
same potential
6 A gG or10 A fast
3 A (C-characteristic)
Setting current
correction
1
1
0.94
1.08
0.88
1.09
0.82
1.1
Last update: 01 April 2011
690
0.8

Advertisement

loading

Summary of Contents for Siemens 3US50

  • Page 1 3US50: 0.1 ... 18 A certified components. 3US55: 6.3 ... 32 A Fig. Ia: 3US50: For mounting on contactors 3TS29 / 30 / 31 / 32, Permissible ambient air temperature -25 °C ..+55 °C Individual mounting possible with assembly kit 3US1950-8.
  • Page 2: Инструкция По Эксплуатации

    3US50: 0.1 ~ 18 A использовании сертифицированных компонентов. 3US55: 6.3 ~ 32 A Рис. Iа: тепловое реле защиты от перегрузки 3US50 для монтажа на кон- Допустимая температура окр. среды - 25 °C ~ + 55 °C такторы 3TS29 / 30 / 31 / 32.
  • Page 3 (I:最小整定电流 I , II:最大整定电流 I ) 小心 ➁ 型号和订货号 只有使用经过认证的部件才能保证设备的正常运转。 技术参数 图 Ia 3US50:与 3TS29 / 30 / 31 / 32 接触器组合安装。 主回路 配用附件 3US1950-8 也可单独安装。 690 V 图 Ib 3US50:与 3TS33 / 34 接触器组合安装。 额定绝缘电压 3US50: 0.1~18 A 配用附件 3US1955-8 也可单独安装。...
  • Page 4 3US50 3US55 IIIa IIIc IIIb L1 L2 L3 RESET AUS-TEST T1 T2 T3 L1 L2 L3 / T1 T2 T3 NO / NC 1 ... 1,5 0,8 ... 1,4 9 ... 13 7 ... 12 2 x 0,5 ... 1 2 x 2,5 ...
  • Page 5 Technical Assistance: Telephone: +49 (0) 911-895-5900 (8°° - 17°° CET) SIEMENS AG Fax: +49 (0) 911-895-5907 Technical Assistance E-mail: technical-assistance@siemens.com Würzburger Str. 121 Internet: www.siemens.com/industrial-controls/technical-assistance D-90766 Fürth Subject to change without prior notice. Store for use at a later date. Order No.: 3ZX3012-0US50-0AY0 © Siemens AG 2011...

This manual is also suitable for:

3us55