Siemens SITRANS LR460 HART Operating Instructions Manual
Siemens SITRANS LR460 HART Operating Instructions Manual

Siemens SITRANS LR460 HART Operating Instructions Manual

Radar transmitters
Hide thumbs Also See for SITRANS LR460 HART:
Table of Contents

Advertisement

Quick Links

Radar Transmitters
SITRANS LR460 HART
Operating Instructions
Edition
09/2017

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SITRANS LR460 HART

  • Page 1 Radar Transmitters SITRANS LR460 HART Operating Instructions Edition 09/2017...
  • Page 2 Siemens AG Industry Sector 76181 Karlsruhe Deutschland • For a selection of Siemens level measurement manuals, go to: www. siemens.com/processautomation. Select Products & Systems, then under Process Level Measurement. Instrumentation, select Manual archives can be found on the Support page by product family.
  • Page 3: Table Of Contents

    Table of Contents Safety Notes .............................1 Safety marking symbols ......................1 FCC and IC Conformity ...........................2 The Manual ...............................3 Technical Support ..........................3 SITRANS LR460 ........................6 Specifications ........................7 Power............................... 7 Performance ............................7 Interface ..............................8 Programmer (infrared keypad) ......................9 Mechanical.............................
  • Page 4 Quick Start Wizard via the handheld programmer .............29 Quick Start Wizard via SIMATIC PDM ...................31 Device Description (DD) ......................31 Quick Start Wizard steps......................32 Level application example ........................36 Auto False Echo Suppression ......................36 Operating SITRANS LR460 via SIMATIC PDM .............37 Functions in SIMATIC PDM ........................37 Features of SIMATIC PDM Rev.
  • Page 5 Fail-safe Mode ............................94 Maximum Process Temperature Chart ....................96 Appendix B: Troubleshooting ..................99 General Fault Codes ......................... 102 Appendix C: Maintenance .................... 105 Unit Repair and Excluded Liability ....................105 Appendix D: Local Operation Interface ..............107 The LCD Display ..........................107 RUN mode (startup display) ....................
  • Page 6 Diagnostics ............................126 Diagnosis reply (applies only to cyclic masters) ...............126 Acyclic Diagnostics ........................126 Extended Mode Diagnosis ......................127 Condensed Mode Diagnosis ....................128 Acyclic Extended Diagnostics (General Fault Codes) ............128 Acyclic Data ............................129 Appendix H: PROFIBUS PA Profile Structure ............131 PROFIBUS Level Device Design ......................131 Block Model for recording and processing measured values ........
  • Page 7: Safety Notes

    Safety Notes Special attention must be paid to warnings and notes highlighted from the rest of the text by grey boxes. WARNING: relates to a caution symbol on the product, and means that failure to observe the necessary precautions can result in death, serious injury, and/or considerable material damage.
  • Page 8: Fcc And Ic Conformity

    Radio Equipment Directive (RED) compliance (Europe) Hereby, Siemens declares that the SITRANS LR460 is in compliance with the essential requirements and other relevant provisions of Directive 2014/53/EU.
  • Page 9: The Manual

    Technical Support Support is available 24 hours a day. To find your local Siemens Automation Office address, phone or fax number go to: www.siemens.com/automation/partner • Click on the tab Contacts by Product and then find your product group (+Process Automation >...
  • Page 10 Abbreviations and Identifications Short Long Form Description Units form Analog to digital AIFB Analog Input Function Block Conformitè Europèene / CE / FM / Factory Mutual / Canadian safety approval Standards Association Internal capacitance Farad Digital to analog Digital Analog Converter Distributed Control System control room apparatus Full Vacuum...
  • Page 11 Short Units Long Form Description form (cont’ d ) Transmitter Variable Time Varying Threshold sensitivity threshold Input voltage Output voltage The output from the Level Transducer Block can be called the Primary Value (or Secondary Value). When it becomes the input to the AIFB, it is called the Process Variable.
  • Page 12: Sitrans Lr460

    Programming SITRANS LR460 carries out its level measurement function according to the set of built-in parameter tables. You can make parameter changes via the Siemens Milltronics handheld programmer, a PC running SIMATIC PDM or other similar software packages. Approvals and Certificates...
  • Page 13: Specifications

    Specifications Siemens Milltronics makes every attempt to ensure the accuracy of these Note: specifications, but reserves the right to change them at any time. SITRANS LR460 Power Power Supply  • 100 to 230 V AC, 15%, 50/60 Hz, 6 W •...
  • Page 14: Interface

      1 mm/year Long-term stability Near Range (blanking) 0.35 m (1.15 ft) Update time mA output and loop display is updated once per second Beam angle • 3" horn: 11° at –3 dB boundary • 4" horn: 8° at –3 dB boundary Memory •...
  • Page 15: Programmer (Infrared Keypad)

    Programmer (infrared keypad) Siemens Milltronics infrared IS (Intrinsically Safe) handheld programmer for hazardous and all other locations (battery is non-replaceable) • approval: ATEX II 1 G EEx ia IIC T4, certificate SIRA 01ATEX2147 CSA and FM Class I, Div. 1, Gr. A, B, C, D T6 @ max.
  • Page 16: Environmental

    Enclosure • construction Die-cast aluminum, painted (polyester powder-coated) • conduit 2 x M20 or 2 x ½” NPT (option) • ingress protection Type 4X/NEMA 4X, Type 6/NEMA 6, IP67 Dust cap (optional) • 3" PTFE, pipe clamp connection, O.D. 95 mm (3.74") •...
  • Page 17: Approvals

    Communication: PROFIBUS PA • Protocol PROFIBUS PA, technology: IEC 61158-2, slave-functionality • Device Profile 3.01 • Device Class Bus current (PROFIBUS PA) 10.5 mA Approvals • Hazardous areas FM/CSA Class II, Div. 1, Groups E,F and G, Class III ATEX II 1 D; 1/2 D, 2D T85 deg C INMETRO BR-Ex tD A20 T85 deg C IP67 •...
  • Page 18: Dimensions

    Dimensions Standard configuration 204 mm (8.0") connection cover electronics cover 287 mm (11.29") purge connection Easy Aimer ball locking bolts universal slotted flange (see page 18 for details) reference point 228 mm (8.97") 285 mm (11.22") horn antenna 74.5 mm 3"...
  • Page 19: Installation

    Installation WARNINGS: • SITRANS LR460 is to be used only in the manner outlined in this manual, otherwise protection provided by the equipment may be impaired. • Installation shall only be performed by qualified personnel and in accordance with local governing regulations. Notes: •...
  • Page 20: Key Considerations

    Key considerations • Correct location is critical to a successful application. • Avoid reflective interference from vessel walls and obstructions by following the guidelines below. WARNINGS: • Do not remove factory lock screw. • Do not rotate upper wave guide with respect to housing or internal change may occur.
  • Page 21: Nozzle Location

    Nozzle location min. 1 m (39") • Locate antenna at least 1 meter away from side wall. • Keep emission cone free of interference from ladders, pipes, I-beams or filling streams. emission • Make allowance for beam spread to cone avoid interference with the emission cone.
  • Page 22: Easy Aimer Installation

    Easy Aimer Installation When the Easy Aimer ball is loosened, the device is free to tilt to a maximum of Note: 30°. Easy Aimer ball locking bolts top clamping plate (upper socket) 0.38" bottom clamping plate (10 mm) (lower socket) customer gasket as required [recommended thickness 1.5 to 1.8 mm (0.06...
  • Page 23: Air Purging System (Optional)

    • Some dust particles are highly abrasive and can be drawn into the inside of the horn during purge cleaning, damaging the internal PTFE emitter of the antenna. A replacement kit is available from your local Siemens Milltronics representative. • It is the customer’s responsibility to ensure that any vacuum or pressure in the measured vessel is maintained, considering the hole that passes through the process connection and SITRANS LR460 antenna system.
  • Page 24: Universal Slotted Flange (For Use With Air Purging Option Only)

    Universal Slotted Flange (for use with Air Purging Option only) WARNING: The user is responsible for the selection of bolting and gasket materials which will fall within the limits of the flange and its intended use and which are suitable for the service conditions. number of slotted bolt holes bolt hole circle max.
  • Page 25: Optional Dust Cap

    Optional Dust Cap The dust cap must be removed before using the Air Purge feature (see Note: Purging System (Optional) on page 17). The dust cap fits onto the end of the horn and prevents the buildup of dust and other process material inside the horn.
  • Page 26 Notes: Page 20 SITRANS LR460 – INSTRUCTION MANUAL A5E42035355...
  • Page 27: Wiring

    Wiring WARNINGS: • Turn off power to the device before unscrewing the housing cover in a hazardous area. • All field wiring for AC models must have insulation suitable for at least 250 V. • The DC input terminals shall be supplied from a source that provides electrical isolation between the input and the output, in order to meet the applicable safety requirements of IEC 61010-1.
  • Page 28: Hart Wiring

    HART wiring LR460 HART requires no power from the 4-20 mA loop. Note: AC version DC version earth earth cable clamp cable clamp terminal terminal Rated temperature of Rated temperature of connection cables must connection cables must exceed maximum ambient 19-30 V exceed maximum ambient temperature by at least 15 K...
  • Page 29: Profibus Wiring

    Tighten the cable gland and check the strain relief (pull and turn). Replace the enclosure cover and hand tighten it. The sealing ring must be clean and undamaged. Tighten the screw on the cover lock. Connect the external earth terminal located cable glands between the cable glands to a ground...
  • Page 30 Connecting PROFIBUS PA Typical PLC/mA configuration with PROFIBUS PA Class 1 Class 2 Master Master PROFIBUS DP DP/PA ET200 Coupler PROFIBUS PA HART SITRANS SITRANS SITRANS LR460 LR460 LR460 Connecting SITRANS LR460 (Continued from on page 21, step 2.) Connect the earth conductor of the power supply to the earth terminal on the metal bracket inside the enclosure.
  • Page 31: Hazardous Area Installations

    SIRA 06ATEX9218X IECEx SIR 06.0058X Ex tD A20 IP67 T85°C Do Not Open in an explosive dust atmosphere. Siemens Milltronics Process Instruments Inc., Peterborough Made in Canada Instructions specific to hazardous area installations (Reference European ATEX Directive 94/9/EC, Annex II, 1/0/6)
  • Page 32 Thermal Data for 7ML5426 Series Permitted ambient Permitted ambient Device temperature at electronic category temperature at horn antenna enclosure –40 °C (–40 °F)  T +200°C –40 °C (–40 °F)  T  +65°C 1D, 1/2D, 2D (+392 °F) (+149 °F) The equipment has not been assessed as a safety related device (as referred to by Directive 94/9/EC Annex II, clause 1.5).
  • Page 33: Quick Start

    Quick Start SITRANS LR460 only supports SIMATIC PDM version 6.0 SP3 (or higher). Note: To set up SITRANS LR460 for a simple application requires only the following settings: • select application type (silo construction) • select operation mode: level, distance or space •...
  • Page 34: Programming Sitrans Lr460

    Programming SITRANS LR460 Activate PROGRAM mode at any time, to change parameter values and set operating conditions. • Parameters are organized into function groups and arranged in a four-level menu LCD Menu Structure structure (see on page 145). • Set parameters to suit your specific application. Parameter Reference •...
  • Page 35: Quick Start Wizard Via The Handheld Programmer

    Quick Start Wizard via the handheld programmer Notes: • The wizard is a complete package and the settings are inter-related. • Do not use the Quick Start wizard to modify individual parameters. See instead Parameter Reference on page 45. (Perform any customization only after Quick Start has been completed.) •...
  • Page 36 Operation types sensor reference point high (flange face) calibration point distance space level low calibration point 1.4. Units Select the units for the Quick Start variables (high and low calibration point, and level, distance, or space). MM, CM, M, IN, FT Options 1.5.
  • Page 37: Quick Start Wizard Via Simatic Pdm

    To use HART or PROFIBUS PA, you will need a PC configuration tool: we recommend SIMATIC PDM. Please consult the operating instructions or online help for details on using SIMATIC PDM. (Application Guides for setting up Siemens PROFIBUS PA and HART instruments with SIMATIC PDM are available on our website: www.siemens.com/processautomation.) Device Description (DD) You will need the DD for SIMATIC PDM version 6.0 SP3 (or higher).
  • Page 38: Quick Start Wizard Steps

    Quick Start Wizard steps Notes: • The Quick Start settings are not independent parameters. The settings are inter- related, and changes only apply when you click Transfer at the end of step 4. • Do not use the Quick Start Wizard to modify individual parameters: see instead Parameter Reference on page 45.
  • Page 39 Step 1 – Identification Click NEXT to accept default values. [Descriptor, Message, and Installation Date (Last config with HART device) fields can be left blank.] * Installation Date field appears as Last config with HART device. Step 2 – Application type Select the application type and operation type and click NEXT.
  • Page 40 Step 3 – Range Setup Set Sensor Units, enter values for Low and High Calibration points, and select a Response Rate just faster than the maximum fill/empty rate. Click NEXT. 1.7. Rate on page 30. Page 34 SITRANS LR460 – INSTRUCTION MANUAL A5E42035355...
  • Page 41 Step 4 – Summary Check parameter settings, and click BACK to return and revise values, or TRANSFER to transfer values to the device. * Installation Date field appears as Last config with HART device. After the values have been transferred to the device the message Device Configuration Complete appears.
  • Page 42: Level Application Example

    Level application example The application is a steel silo containing flour that takes an average 3 hours to fill and 3 weeks to empty. Using the Easy Aimer, the LR460 is oriented so that the emission cone is approximately perpendicular to the material surface. Fill rate = 0.09 m/minute (15.5 / 180).
  • Page 43: Operating Sitrans Lr460 Via Simatic Pdm

    Please consult the operating instructions or online help for details on using SIMATIC PDM. (You can find more information at https:// pcs.khe.siemens.com/index.aspx?nr=3695.) Functions in SIMATIC PDM SIMATIC PDM monitors the process values, alarms and status signals of the device. It allows you to display, compare, adjust, verify, and simulate process device data.
  • Page 44: Echo Profile Saving And Viewing

    Echo profile saving and viewing Double click each axis and record the Xscale and Data Scale values, so that you Note: can restore the default view by resetting to these values. • Open the menu View – Echo Profile. • Press Measure to update an echo profile.
  • Page 45: Manual Tvt Shaper

    Manual TVT Shaper Notes: Auto False-Echo Suppression • For a more detailed explanation see on page 93. 3.5.6. TVT (Auto False Echo Suppression) Setup • See on page 63 for more instructions. • Double click each axis and record the Xscale and Data Scale values, so that you can restore the default view by resetting to these values.
  • Page 46: Accessing Functions In Pdm

    Accessing Functions in PDM You have access to a number of functions via pull-down menus from the menu bar under Device or View. Pull-down menus for HART via SIMATIC PDM Pull- For a complete list see on page 45 or down menus for PROFIBUS PA via SIMATIC PDM on page 46.
  • Page 47: Changing Parameter Settings Via Simatic Pdm

    Changing parameter settings via SIMATIC PDM Parameter Reference For a complete list of parameters, see on page 45. Note: Launch SIMATIC PDM, connect to SITRANS LR460, and upload data from the device. Adjust parameter values in the parameter value field then press Enter. The status fields read Changed.
  • Page 48: Configuration Flag Reset (Hart Only)

    Warm Start This has the same effect as cycling power. It does not reset any parameters. • Open the menu Device – Reset, select Warm Start and click OK. Configuration Flag Reset (HART only) To reset the configuration flag to zero, open the menu Device – Configuration Flag Reset and execute a reset.
  • Page 49 1. Open the menu Device – Simulation, and select the desired function block. 2. From the Simulation (Measured Value) tab, enable simulation, enter a value, and click Transfer. 3. After simulation is complete, disable simulation. Simulation (Output) (PROFIBUS PA only) Allows you to simulate the output value from a Function Block.
  • Page 50 Notes: Page 44 SITRANS LR460 – INSTRUCTION MANUAL A5E42035355...
  • Page 51: Parameter Reference

    Parameter Reference Parameter menus The parameters are grouped in menus according to function. Submenus arranged on four levels give access to associated features and options. Parameters accessible via the handheld programmer are preceded by a number. (See LCD Menu Structure on page 145 for a chart.) Parameters not preceded by a number are accessible only via SIMATIC PDM.
  • Page 52: Pull-Down Menus For Profibus Pa Via Simatic Pdm

    Pull-down menus for PROFIBUS PA via SIMATIC PDM Device menus page View menus page Communication path Display Trend Echo Profile Download to Device Show Echo Profile* Upload to PC/PG Device Status Update Diagnostic Status Clear Faults Peak Values Wear Toolbar Set Address Status Bar Quickstart...
  • Page 53: Quick Start Wizard

    Quick Start Wizard The Quick Start wizard groups together all the settings you need to make for a simple application. • The wizard is a complete package and settings are inter-related. • Do not use the wizard to modify individual parameters. (Perform any customization only after Quick Start has been completed.) •...
  • Page 54 1.4. Sensor Units (UNITS) Select the units for the Quick Start variables (high and low calibration point, and level, distance, or space). MM, CM, M, IN, FT Options 1.5. High Calibration Point (CAL HIGH) Distance from Sensor Reference to High Calibration Point: usually process full level (see illustration to 1.3) Range: 0.0000 to 100.00 m Values...
  • Page 55: Identification (Ident)

    Default settings in the parameter tables are indicated with an asterisk (*) unless Note: explicitly stated 2. Identification (IDENT) Operation Unit Text that can be used in any way, for example as a unique label for a field device in the plant. Descriptor Text that is associated with the Field Device.
  • Page 56 Two Reset options are available via SIMATIC PDM. Selecting Factory Defaults resets all parameters excluding device addresses to default values. Reset (Warm Start) has the same effect as recycling power. HART Description No reset performed. NONE Resets all parameters to the manufacturer’s default settings with the following exceptions: Handheld...
  • Page 57 2.1.8. Backlight Controls the setting for the LCD backlight feature. Backlight off Handheld Backlight on programmer Backlight remains illuminated for 3 minutes from last key Values press. 2.1. Configuration (CONFIG) (for PROFIBUS PA devices) Configuration (CONFIG) (for HART devices) 2.1. on page 49 to configure HART devices.
  • Page 58 PROFIBUS Description Resets all parameters to the manufacturer’s default settings with the following exceptions: • tag, descriptor, message and device addresses are not Factory defaults reset (FACTORY) • Lock and Unlock values are not reset • the learned TVT curve is not lost PDM Options Standard...
  • Page 59 To perform a Reset via the handheld programmer: a. Press Mode to open PROGRAM mode, and key in 216 for Quick Access, or use ARROW keys to navigate to menu IDENT–CONFIG–ACK FAULT. b. Key in the number of the fault you want to clear. c.
  • Page 60 GSD file (the GSD file provides information on the device to the master). Profile-specific [uses generic GSD for 2 AIFB (ident # = 0x9701)] Manufacturer-specific [uses Siemens DD and GSD file, which identifies the LR460 (PROFIBUS PA)] (ident # = Values...
  • Page 61: Input

    2.3. Statistics (STATS) To view Statistics via PDM, open the menu View – Wear. 2.3.1. Total Device Operating Time (PWRD HOURS) Number of hours the unit has been powered up since manufacture. 2.3.2. Poweron Resets (RESETS) The number of power cycles that have occurred since manufacture. 3.
  • Page 62 3.3. Sensor Calibration (SENSOR CAL) Quick Start Wizard via the To perform calibration for a simple application go to handheld programmer Quick Start Wizard via SIMATIC PDM on page 29 or on page To modify an individual parameter setting, do not use the Quick Start wizard. LR460 with Easy Aimer Sensor Reference Point (flange face)
  • Page 63 3.3.4. High Calibration Pt. (CAL HIGH) Distance from Sensor Reference to High Calibration Point (corresponding to High Level Point). Unit is defined in Sensor units. Range: 0 to 100 m Values Default: 0 m 3.3.5. Unit (Level) (LVL UNIT) Selected engineering units for Level (PV), referenced from Low Level Point (plus level offset, if any).
  • Page 64 3.3.A. Temperature Units (TEMP UNIT) Selects the engineering unit to be displayed with the value representing temperature. C, F, R, K Options default: °C 3.4. Measuring Limits (MEAS LIM) You can view maximum and minimum values for the sensor values and the process temperature.
  • Page 65 3.5. Detailed Setup (DT SETUP) 3.5.1. Fail-safe 3.5.1.1. LOE (Loss of Echo) Timer (LOE TIME) Amount of time, in minutes, that a Loss of Echo must persist, before the device goes into Fail-safe mode. See Fail-safe Mode for more details. Range: 0.00 to 720 (minutes) Values Default: 10.000...
  • Page 66 3.5.2.2. Threshold Long (THRSH LONG) Sets the minimum echo confidence that the echo must meet in order to prevent a Loss of Echo condition and the expiration of the LOE timer. When Echo Confidence exceeds the Confidence Threshold, the echo is evaluated. Range: 0 to 99 Values Default: 10...
  • Page 67 3.5.2.5. Reform Echo (REFORM) Smooths jagged peaks in the echo profile. Reforms fragmented echoes into one echo. 0 = OFF Default = 0 Values Greater = Wider Recommended range 10 to 20: higher is not recommended. • Material Related 3.5.2. 1 . Algorithm •...
  • Page 68 3.5.3.3. Shots The number of echo profile samples averaged to produce a measurement. Range: 1 to 25 Values Default: 15 3.5.4. Range Sensor Reference Point (flange face) High Calibration Point Near Range Level Low Calibration Point Far Range 3.5.4.1. Near Range The range in front of the device (referenced from the flange face) within which any echoes will be ignored.
  • Page 69 3.5.6. TVT (Auto False Echo Suppression) Setup If the Reform parameter has been used to reshape the echo profile, Note: Auto False Echo Suppression must be re-enabled, to relearn the TVT curve SITRANS LR460 first learns the echo profile. Then the learned profile, or part of it, is used to screen out false echoes.
  • Page 70 To use Auto False Echo Suppression via SIMATIC PDM: Determine Range (the distance within which the learned TVT will replace the default TVT). Measure the actual distance from the antenna reference point to the material surface using a rope or tape measure, and make allowances for the actual location of the LR460.
  • Page 71 Display before Auto False Echo Suppression default material surface false echo Echo Marker Example after Auto False Echo Suppression material surface learned TVT curve false echo A5E42035355 SITRANS LR460 – INSTRUCTION MANUAL Page 65...
  • Page 72 3.5.6.3. TVT Hover Level (TVT HOVER) Defines in percent how high the TVT (Time Varying Threshold) curve is placed above the echo profile, with respect to largest echo. Range: 0 to 100% Values Default: 33% 3.5.6.4. Shaper Mode (SHAPER MD) Enables the TVT curve to be manually adjusted at a specified range.
  • Page 73 3.5.7.4. Shaper D (28 - 36) 3.5.7.5. Shaper E (37 - 45) 3.5.7.6. Shaper F (46 - 54) 3.5.7.7. Shaper G (55 - 63) 3.5.7.8. Shaper H (64 - 72) 3.5.7.9. Shaper I (73 - 81) 3.5.7.A. Shaper J (82 - 90) 3.5.7.B.
  • Page 74: Output

    3.6. Echo Information (ECHO INFO) 3.6.1. Level Transducer Block (TB VALUES) (for diagnostic purposes) The output from the Level Transducer Block can be called the Primary Value (or Secondary Value). When it becomes the input to the AIFB, it is called the Process Variable.
  • Page 75 4.1.1. Target Mode (TARGET MDE) Used to request an operating mode from the Function Block. Out of Service Manual Mode Values AUTO Automatic Mode In SIMATIC PDM (PROFIBUS PA only) open the menu Device – Simulation, and select the appropriate function block menu. Select the tab Simulation (Output) and see Target Mode.
  • Page 76 4.1.5.1. Batch ID Identifies a certain batch to allow assignment of equipment-related information (for example faults, alarms) to the batch. Range: 0 to 4294967295 Values Default: 0 4.1.5.2. Batch Unit Identifies the active Control Recipe Unit Procedure or the related Unit (for example, reactor, centrifuge, drier).
  • Page 77 4.1.6. Process Value Scale (PR VAL SCL) 4.1.6.1. Lower Value (LOWR VALUE) Defines the operational lower range value of the input value (Process Value Scale) in engineering units. Process Value Scale normalizes the input value to a customer-defined range. Range: -999999 to 999999 m Values Default: 0 m 4.1.6.2.
  • Page 78 4.1.7.1. Lower Value (LOWR VALUE) Defines the operational lower range value of the output value in engineering units. Range: -999999 to 999999 m Values Default: 0 m 4.1.7.2. Upper Value (UPPR VALUE) Defines the operational upper range value of the output value in engineering units.
  • Page 79 4.1.8.5. Limit Hysteresis (LIMIT HYS.) Hysteresis is used to adjust the sensitivity of the trigger for alarm messages. It is used to compensate when a process variable fluctuates around the same value as a limit. A high level alarm occurs when a value exceeds an upper limit.
  • Page 80 4.1.A. Human Interface (INTERFACE) 4.1.A.1. Decimal Point (DECIMAL) The number of digits to display after the decimal point. (The LCD is limited to displaying three decimal places.) Out unit text If the code list does not contain a desired unit for the OUT parameter, (see General Requirement) you can write the specific text in this parameter.
  • Page 81 4.3.3. Man Value A user-defined mA value which can be used either for simulation, or to do a digital/analog trim. Range: 3.5 to 22.6 mA Values To set the mA Output via PDM, open the menu Device – Simulate AO and select an option.
  • Page 82 4.3.8. 4 mA Trim (4MA TRIM) Calibrates the 4 mA output. Range: 2.0 to 6.0 mA Values 4.3. 1 . Function Related A mA value derived from the ratio of current level to the range between Lower Value (LOWR VALUE) and Upper parameters Value (UPPR VALUE).
  • Page 83 4.4.2. Relay Function (FUNCTION) DISABLED * Relay is disabled and will not trigger Relay state can be changed (using MANUAL 4.4.4. Relay State (STATE) parameter Relay triggers when corresponding AIFB LO ALM goes below low alarm Handheld programmer Relay triggers when corresponding AIFB HI ALM goes above high alarm Options...
  • Page 84 To access these parameters via SIMATIC PDM open the menu Device – Maintenance and select the Remaining Device Lifetime tab. 6.1.1. Total Device Operating Time (DVC OP TIM) Read only. Displays the amount of time the device has been operating. 6.1.2.
  • Page 85 6.1.4. Maintenance Demanded Limit (DEM LIMIT) If the Total Expected Device Life less Total Device Operating Time is equal to or less than this limit, a Maintenance Demanded status is generated. Range: 0 to 20 years Values Default: 0.019 years To modify the value via SIMATIC PDM: a.
  • Page 86 6.1.7. Status (MAINT STAT) Read only. Displays the status of the Maintenance Alerts. NONE None Options MAINT REQ Maintenance Required (read only) MAINT DEM Maintenance Demanded To view via SIMATIC PDM open the menu View - Device Status (PROFIBUS PA) or View –...
  • Page 87 To acknowledge an alert via SIMATIC PDM: a. Open the menu View - Device Status (PROFIBUS PA) or View – Status (HART), and click on the Maintenance tab. b. In the Device Lifetime window click on Acknowledge Warnings. IGNORE Options (read only) ACK WARNING 6.2.
  • Page 88 6.2.3. Maintenance Required Limit (REQ LIMIT) If the Total Expected Sensor Life less Total Sensor Operating Time is equal to or less than this limit, a Maintenance Required status is generated. Range: 0 to 20 years Values Default: 0.164 years To modify the value via SIMATIC PDM: a.
  • Page 89 6.2.6. Total Expected Sensor Life (EXP LIFE) The device tries to predict its overall lifetime. You can reset the factory default. Range: 0 to 20 years Values Default: 10.00 years To modify the value via SIMATIC PDM: a. Open the menu Device – Maintenance and click on Remaining Sensor Lifetime.
  • Page 90 To view via SIMATIC PDM open the menu View - Device Status (PROFIBUS PA) or View – Status (HART), click on the Maintenance tab, and check the Sensor Lifetime Status window. * only Status, Maintenance, and Diagnostics tabs appear with HART device. 6.2.8.
  • Page 91 6.3. Service Interval (SERVICE) Allows for scheduling of service inspections. To access these parameters via SIMATIC PDM, open the menu Device – Maintenance and click on the Service Interval tab. 6.3.1. Time Lapsed From Last Service (LAST SVC) Read only. Time elapsed since device was last serviced. Can be reset to zero via the handheld programmer (after performing a service).
  • Page 92 6.3.6. Status (MAINT STAT) Read only. Displays the status of the Maintenance Alerts. NONE None Options MAINT REQ Maintenance Required (read only) MAINT DEM Maintenance Demanded In SIMATIC PDM, open the menu View - Device Status (PROFIBUS PA) or View –...
  • Page 93 6.4.2. Maintenance Required Limit (REQ LIMIT) If the Total Calibration Interval less the Time Lapsed from Last Calibration is equal to or less than this limit, a Maintenance Required status is generated. Range: 0 to 20 years Values Default: 0.164 years 6.4.3.
  • Page 94: Condensed Status Setup (Cond Setup) (Profibus Pa Only)

    In SIMATIC PDM, open the menu View - Device Status (PROFIBUS PA) or View – Status (HART), click on the Maintenance tab and check the Calibration Interval window. 6.4.7. Acknowledge (ACK STATUS) Read only: displays the status of the Maintenance Alerts that have been acknowledged.
  • Page 95 Lists those features that have been enabled. 7.4. Event Switch (EVNT SWTCH) 7.4.1. Event Index (EVNT INDEX) The numeric component of the Event Code for a Condensed Status event. For example, the Event Code (status designation ) for Loss of Echo (LOE) is S0: the Event Index is 0.
  • Page 96 To assign a status to a particular event via the handheld programmer: a. Go to Condensed Status Mode (COND STAT) (7.1.) and select Yes to enable Condensed Mode. b. In Event Index (EVNT INDEX) (7.4.1.) enter the event index number corresponding to a particular event.
  • Page 97: Appendix A: Technical Reference

    Appendix A: Technical Reference Principles of Operation SITRANS LR460 is a long range FMCW (Frequency Modulated Continuous Wave) radar transmitter. Radar level measurement uses the time of flight principle to determine distance to a material surface. FMCW radar transmits a continuous wave. The frequency of the wave is constantly increasing: this is known as the sweep.
  • Page 98: Echo Processing

    Echo Processing Profile monitoring via SIMATIC PDM To view an echo profile open the menu View – Echo Profile. echo profile TVT curve echo distance You will see the echo profile, the Time Varying Threshold (TVT), and a vertical line indicating the distance from the sensor to the echo selected.
  • Page 99: False Echoes

    False Echoes False echoes can appear during the receive cycle. They can be caused by interference with the emission cone, or by internal impediments like a ladder rung, and are usually indicated by an incorrect high level reading. Beam angle at –3dB reference Make allowance for the beam 3"...
  • Page 100: Near Range (Blanking)

    Near Range (Blanking) Auto False-Echo Suppression is generally recommended in preference to using Note: Near Range. Near Range allows you to set a distance in front of the antenna, within which any echoes will be ignored. Echo confidence Echo confidence is an internally generated numeric rating given to an echo based on its relative strength, area, and height.
  • Page 101 The Fail-safe condition may be triggered by a loss of echo, a bad configuration, or certain device faults. You can select one of three possible values to be reported when a Fail-safe mode occurs: • User-defined default value (Fail-safe value) used as output value. •...
  • Page 102 Maximum Process Temperature Chart WARNING: Internal temperature must not exceed +85 C (+185 The chart below is for guidance only. Note: To check maximum and minimum temperatures recorded via SIMATIC PDM, open the menu View – Peak Values, and click on the temperature tab. The peak temperatures indicate the extent of change required to the installation in order to provide a reliable thermal-operating zone for SITRANS LR460.
  • Page 103 ambient • The chart above is provided for temperature guidance only. • It does not represent every possible process connection arrangement. flange • It does not take into consideration temperature heating from direct sunshine exposure. process temperature Where the chart does not apply, please use your own judgement regarding the use of SITRANS LR460.
  • Page 104 Notes Page A-98 SITRANS LR460 – INSTRUCTION MANUAL A5E42035355...
  • Page 105 Check the HART (or PROFIBUS) address and make sure all devices are at unique HART (or PROFIBUS) addresses. If you continue to experience problems, go to our website at: www.siemens.com/processautomation, and check the FAQs for SITRANS LR460, or contact your Siemens Milltronics representative. Troubleshooting LR460...
  • Page 106 Troubleshooting LR460 (cont’ d ) Symptom Possible cause Remedy Increase TVT manually at vessel bottom Reads empty Reads vessel bottom region. when vessel not through low dK material. Set Far Range to a lower value. empty. Lower TVT hover level. Due to solids’...
  • Page 107 Troubleshooting LR460 (cont’ d ) Symptom Possible cause Remedy The PLC value • scaling in AIFB1 is equals the incorrect display value, • High Calibration Point is • Adjust scaling in AIFB but does not incorrectly entered • Correct High Calibration Point setting correspond to •...
  • Page 108 Possible causes: faulty minimize foaming. If problem installation, material buildup, persists, contact your local and/or presence of foam. Siemens representative. Device is nearing its lifetime Replacement is limit according to the value recommended. set in Maintenance Required Limit.
  • Page 109 Byte Meaning (cont’ d ) Corrective Action display (cont’ d ) Check calibration settings of Input parameters High device. Ensure settings for Calibration Point and Low High Calibration Point and S:10 Calibration Point are the Low Calibration Point are same. different.
  • Page 110 Repair required: contact your EEPROM damaged. local Siemens S:29 representative. Reset power. If error persists, EEPROM corrupt. contact your local Siemens S:30 representative. Repair required: contact your Flash error. local Siemens S:31 representative. Ensure value of the Ident...
  • Page 111 Please note the following: • The user is responsible for all changes and repairs made to the device. • All new components must be provided by Siemens Milltronics Process Instruments Inc. • Restrict repair to faulty components only.
  • Page 112 Notes: Page C-106 SITRANS LR460 – INSTRUCTION MANUAL A5E42035355...
  • Page 113 2 – Parameter name 0.01.18 3 – Edit Mode indicator/PROGRAM icon 4 – Value of current parameter LOE Timer on page 94 for details. Appears in response to request via Siemens Milltronics handheld programmer A5E42035355 SITRANS LR460 (HART) – INSTRUCTION MANUAL Page D-107...
  • Page 114 The handheld programmer Notes: Local Operation Enable • Local programming must be enabled, to allow changes (see on page 54). • CLEAR can be used to clear the field. • Press Right ARROW to open Edit mode: the PROGRAM icon flashes. •...
  • Page 115 • In Navigation mode the rightmost digit of the menu number flashes and the PROGRAM icon is not visible. • In Edit Mode the PROGRAM icon appears and flashes: press a number key to enter parameter data. Hand-held programmer: key functions in Navigation mode When Name Navigation Mode...
  • Page 116 Notes: Page D-110 SITRANS LR460 (HART) – INSTRUCTION MANUAL A5E42035355...
  • Page 117 You can download the HART DD for SITRANS LR460 from the product page of our website. Go to: www.siemens.com/lr460 and click on Downloads. Older versions of the library will have to be updated in order to use all the features of SITRANS LR460.
  • Page 118 HART Version SITRANS LR460 conforms to HART rev. 5.1. HART Burst Mode SITRANS LR460 does not support Burst Mode. HART Communication Parameter Warning: Incorrect use of this parameter can cause all communication to be lost. To set the number of preamble requests open the menu Device – HART Communication. Page E-112 SITRANS LR460 (HART) –...
  • Page 119 HART Communicator 375 Menu Structure HART Communicator 375 is supported by SITRANS LR460 HART. The menu structure Note: is aligned with the menu structure of SIMATIC PDM. SITRANS LR460 DD-Version Identification Operation Unit Description Message Device Manufacturer Product designation Device Serial Number Order No.
  • Page 120 Range Near Range Far Range TVT Setup Auto False Echo Suppression Range TVT Hover Level Shaper Mode TVT Shaper Shaper 1-9 (Shaper Points 1-9) Shaper 10-18 (Shaper Points 10-18) Shaper 19-27 (Shaper Points 19-27) Shaper 28-36 (Shaper Points 28-36) Shaper 37-45 (Shaper Points 37-45) Shaper 46-54 (Shaper Points 46-54) Shaper 55-63 (Shaper Points 55-63) Shaper 64-72 (Shaper Points 64-72)
  • Page 121 Output Limits Lower Limit Alarm Upper Limit Alarm Limit Hysteresis Human Interface Decimal Point Out unit text mA Output mA Allocation mA min Limit mA max limit Failsafe Mode Failsafe Value Relay Configuration Relay AIFB Relay Function Relay NO/NC Relay State Device Certification Maintenance Settings Remaining Device Lifetime...
  • Page 122 Notes: Page E-116 SITRANS LR460 (HART) – INSTRUCTION MANUAL A5E42035355...
  • Page 123 Appendix F: HART Information Structure SITRANS LR460 detects a material level via the sensor, and then processes that information to provide a measured value. The measured value is conveyed as a digital signal. The LR460 device design enables it to provide outputs to two different channels: •...
  • Page 124 Analog Input Function Blocks AIFB1 and AIFB2 The two AIFBs are identical, but completely independent of each other. They utilize the output from the Level Transducer Block. You set parameters for each AIFB in order for it to apply any required quality checks, scaling, and Fail-safe Operation selections.
  • Page 125 The GSD file The GSD file SIEM8132.gsd is available from the SITRANS LR460 product page on our web site. Go to www.siemens.com/lr460 and click Downloads. Bus Termination PROFIBUS PA MUST be terminated at both extreme ends of the cable for it to Note: work properly.
  • Page 126 Profile Model which can identify a product as a generic profile device on the network. SITRANS LR460 can be identified in one of three ways: Device Identification Profile Model Manufacturer-specific [uses Siemens DD and GSD file, which SITRANS LR460 identifies the LR460 (PROFIBUS PA)]. 1 Analog Input Function Block...
  • Page 127 If SITRANS LR460 is not listed in the STEP 7 device catalog, you can download the GSD file from our website and install it in STEP 7. Go to: www.siemens.com/lr460 and click Downloads. Add the SITRANS LR460 "rack": click and drag the SITRANS LR460 folder from the hardware catalog.
  • Page 128 AIFB1 and AIFB2 return 5 bytes of data each: Floating Point Status byte 1 byte 2 byte 3 byte 4 byte 5 AIFB1 byte 6 byte 7 byte 8 byte 9 byte10 byte10 AIFB2 The first 4 bytes are the floating point representation (IEEE) of the variable. The variables are the outputs of the function block.
  • Page 129 Status Codes for Bad Quality Values in hex notation Description The LOE timer has expired: this could be caused by 0x10 LOE or by a sensor malfunction: value is BAD. There is an error in the configuration of the function 0x01 blocks in PROFIBUS PA The function block, or the transducer block, has been...
  • Page 130 Condensed Status 7. Condensed Status These codes are available when Condensed Status is enabled. See Setup (COND SETUP) (PROFIBUS PA only) on page 88. for more details. Condensed Status Codes for Good Quality Status – GOOD Description value No error or special condition is associated with this 0x80 GOOD –...
  • Page 131 Condensed Status Codes for Uncertain Quality (cont’ d ) Status – Description (cont’ d ) value UNCERTAIN Indicates the start of a simulation. Simulation of a measured value or Input FB mode changes from AUTO to MAN. • This status remains active for at least 10 seconds: –...
  • Page 132 Diagnostics All diagnostic information shown below is viewable via PDM. Diagnosis reply (applies only to cyclic masters) During DPV0 data exchange, the PROFIBUS PA slave will notify the Master when a serious error occurs. The Master will then send a Diagnosis request. The reply to this request is normally logged in the PLC and is referred to as the "Hex values."...
  • Page 133 Extended Mode Diagnosis Extended Mode Diagnosis Indication Hex values Byte Description class 0x01000000 Electronics failure 0x02000000 Mechanical failure 0x04000000 Motor Temperature too high 0x08000000 Electronics temperature too high 0x10000000 Memory error 0X20000000 Measurement failure 0X40000000 Device not initialized (no calibration) 0x80000000 Self calibration failed 0x00010000...
  • Page 134 Condensed Mode Diagnosis Condensed Mode Diagnosis Indication Hex values Byte Description class 0x00000800 New startup carried out (Warm Start) 0x00001000 Restart carried out (Cold Start) 0x00002000 Maintenance required Reserved for use within the PNO Set to 1 (one), if the Ident_Number of the running cyclic data transfer and the value of 0x00008000 Physical Block IDENT_NUMBER_SELECTOR...
  • Page 135 Acyclic Data SITRANS LR460 supports up to four simultaneous connections by a Class 2 Master (C2 connection). It supports one connection by a Class 1 Master (C1 connection). In order for a Class 1 Master to read parameters from an instrument, it needs to know the slot and absolute index of the parameter.
  • Page 136 Notes: Page G-130 SITRANS LR460 (PROFIBUS PA) – INSTRUCTION MANUAL A5E42035355...
  • Page 137 Appendix H: PROFIBUS PA Profile Structure PROFIBUS Level Device Design The device follows the profile block model and is implemented as a Profile 3.01, Class B, PA device. Standard profile parameters are used to program the Level Transducer Block. Block Model for recording and processing measured values The functions of the device are divided into blocks for different areas of responsibility.
  • Page 138 Description of the blocks Level Transducer Block function groups Note: Primary Value (PV) is the default measured value; Secondary Value 1 (SV1) is an equivalent value. The figure below shows the signal flow of measured values from the sensor through the Level Transducer Block into the output value (Primary Value/ Level;...
  • Page 139 Level Calibration is a linear transfer function that converts a sensor value to a level value. Level High Level Point Level Value Low Level Point Calibration Low Calibration Point Sensor Value High Calibration Point Sensor Reference Point (flange face) SV2 (distance) High Level Point High Calibration Point Level...
  • Page 140 Electronics temperature The Level Transducer Block also monitors the internal temperature of the device electronics. If the temperature exceeds permitted limits, it does not change the sensor value, but it does change the status.The permitted limits correspond to those of the permitted ambient temperature.
  • Page 141 Output Conversion Values transmitted by the TB have a status attached. The decision on what to do with each value is made by the Analog Input Function Block. Device/ Input Simulation The input can be a simulated value instead of a TB OUT value. This allows the AI block to be tested independently of the characteristics of the environment.
  • Page 142 The unit of the limits corresponds to the unit of the output range. A hysteresis parameter prevents toggling in the Status field of the OUT value.) The status of the Process Variable (input value) is checked. If the status is Bad, a Fail-safe condition occurs.
  • Page 143 Appendix J: Software Revision History The software revision number of the device is shown on the sticker on the Note: product. PROFIBUS PA Software DD Rev. Date Changes Rev. 1.04.02 1.04.04 Jun. 29, 2007 • Initial release. • No longer reports an incorrect 1.04.04 1.04.04 Apr.
  • Page 144 Notes Page J-138 SITRANS LR460 – INSTRUCTION MANUAL A5E42035355...
  • Page 145 Glossary accuracy: degree of conformity of a measure to a standard or a true value. agitator: mechanical apparatus for mixing or aerating. A device for creating turbulence. algorithm: a prescribed set of well-defined rules or processes for the solution of a problem in a finite number of steps.
  • Page 146 dielectric constant (DK): the ability of a dielectric to store electrical potential energy under the influence of an electric field. Also known as Relative Permittivity. An increase in the dielectric constant is directly proportional to an increase in signal amplitude. The value is usually given relative to a vacuum /dry air: the dielectric constant of air is 1 echo: a signal that has been reflected with sufficient magnitude and delay to be perceived in some manner as a signal distinct from that directly transmitted.
  • Page 147 polarization error: the error arising from the transmission or reception of an electromagnetic wave having a polarization other than that intended for the system. PROFIBUS PA: part of the PROFIBUS protocol that is specifically tailored for the needs of process industries (PA = Process Automation). propagation factor (pf): where the maximum velocity is 1.0, pf is a value that represents a reduction in propagation velocity as a result of the wave travelling through a pipe or medium.
  • Page 148 Notes Page 142 SITRANS LR460 – INSTRUCTION MANUAL A5E42035355...
  • Page 149 Index echo confidence explanation 94 echo monitoring level trend diagram 38 abbreviations profile saving 38 list 4 echo status indicator accuracy reliable echo 107 specifications 7 unreliable echo 107 activating LR460 27 address 49 factory reset application example 36 performing 49 approvals 11 via PDM 41 Auto False-Echo Suppression...
  • Page 150 cleaning 105 cautions 105 maintenance settings 77 excluded liability 105 measure key 108 reset parameters measurement response factory reset 49 explanation 91 individual via handheld programmer mounting location 13 via PDM 41 RUN mode display 27 Near Range explanation 94 safety marking symbols 1 setting 62 safety notes 1...
  • Page 151 LCD menu structure SITRANS LR460 – INSTRUCTION MANUAL Page 145 SITRANS LR460 – INSTRUCTION MANUAL A5E42035355...
  • Page 152 LCD menu structure QUICK START DT SETUP FAIL-SAFE 1. QUICK START 1. LANGUAGE 1. FAIL-SAFE 1. LOE TIME CONFIG (HART) 2. APPL 2. ECHO SEL 2. RESTRICT 3. OPERATION 2. ADDR 3. ECHO SAMP 4. UNITS 3. REMLOCK ECHO SEL 4.
  • Page 153 LCD menu charts (continued) AIFB1 OUTPUT 1. TARGET MDE 4. OUTPUT 1. AIFB 1 2. UNIT 2. AIFB 2 BATCH 3. FILT TIME 3. mA OUTPUT (PROFIBUS PA) 4. CHANNEL 4. RLY CONFIG 1. BATCH ID 5. BATCH 2. BATCH UNIT 6.
  • Page 154 LCD menu charts (continued) DVC REMLIF MAINT SET 6. MAINT SET 1. DVC REMLIF 1. DVC OP TIM 2. SNS REMLIF 2. RESTLIFE 3. SERVICE 3. REQ LIMIT 4. CAL 4. DEM LIMIT 5. ACTIVATION 6. EXP LIFE 7. MAINT STAT 8.
  • Page 155 For more information www.siemens.com/level www.siemens.com/weighing Siemens Canada Limited 1954 Technology Drive Printed in Canada P.O. Box 4225 Subject to change without prior notice A5E42035355 Rev. AA Peterborough, ON Canada K9J 7B1 © Siemens AG 2017 www.siemens.com/processautomation...

Table of Contents