Simulated VRF capacity increase time-delay when SW1-1 ON is defined below:
SW1-5
SW1-6
Default vane position on power up.
SW1-7
SW1-8
SW1-9
Fan mode operation (G signal)
*By switching SW1-9 to ON; during 5 minutes Fan OFF cycle (G signal will be disabled) allows other
indoor unit(s) to enter heating thermal ON.
SW1-10
FAN speed during 1
*Powerful fan speed may not be available on all models; fan speed will automatically revert to highest
available speed.

4.0 System Configuration

Device Configuration:
Initial settings can be configured via the DIP switches on the RMF-CA200-V2 controller board. Request codes not addressed by RMF-CA200-
V2 may be configured by temporarily connecting an MA remote controller. Please reference product(s) manual for setting details.
For residential systems (M & P-Series): Temporary connection of an MA controller may be required for configuration of function settings.
For City-Multi systems: Configuration of mode settings must be configured with Maintenance Tool, please refer to product manual for details.
Grouping:
The connection of more than one RMF-CA200-V2 to a single thermostat is not supported.
Temperature Sensing:
The RMF-CA200-V2 relies upon both the dry-contact thermostat inputs andMitsubishi Electric indoor unit's thermistors to monitor room
temperature. The thermostat senses room temperature and establishes indoor unit's set temp. The Mitsubishi Electric indoor unit's return air
thermistor is used for cooling and heating set-point calculation.
IM-RMF-CA200-V2-202306FM
10 Minute
5 Minute
15 Minute
Automatic
Position 1
Normal fan
Fan operation – 20 minutes ON; 5 minutes OFF
operation
(Recommended for Ported Style Multi-Zone
and 2
stage heating and cooling
st
nd
1
Stage – Medium; 2
Stage –
st
nd
Powerful*
© Mitsubishi Electric Sales Canada Inc. All rights reserved.
20 Minute
Position 5
Swing
Systems)*
1
Stage – Low; 2
Stage – High