8. COMPRESSOR CONTROL

1. OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in the Table 10.
(Table 10 : Compressor frequency range)
AOU9/ 12RLFF
AOU15RLFF
2. OPEARTION FREQUENCY CONTROL AT NORMAL START UP
The compressor frequency soon after the start-up is controlled as shown in the Fig.10
(Fig.10 : Compressor control at start-up)
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
(Frequency)
AOU9/ 12RLFF
AOU15RLFF
(Time)
AOU9/ 12 / 15RLFF
3. LIMITATION OF COMPRESSOR FREQUENCY BY OUTDOOR TEMPERATURE
The minimum compressor frequency is limited by outdoor temperature as shown in the Table11.
(Table11 : Limitation of Compressor Frequency)
[ Cooling/ Dry ]
AOU9/ 12RLFF
AOU15RLFF
[ Heating ]
AOU9/ 12RLFF
AOU15RLFF
Cooling
Minimum
Maximum
10rps
76rps
12rps
91rps
Time
Time
Frequency
Frequency
40rps
57rps
40rps
59rps
Time
Time
80sec
110sec
50°F (10°C)
59°F (14°C)
Under
Over
Under
35rps
18rps
32°F (0°C)
50°F (10°C)
Under
Over
Under
24rps
18rps
-4°F (-20°C)
5°F (-15°C)
Under
Over
Under
35rps
35rps
-4°F (-20°C)
5°F (-15°C)
Under
Over
Under
24rps
24rps
Heating
Minimum
Maximum
16rps
119rps
16rps
140rps
Time
Time
Time
Frequency
Frequency
Frequency
72rps
80rps
72rps
80rps
Time
Time
Time
140sec
200sec
350sec
104°F (40°C)
Over
Under
Over
10rps
10rps
104°F (40°C)
Over
Under
Over
12rps
16rps
23°F (-5°C)
Over
Under
Over
Under
35rps
29rps
23°F (-5°C)
Over
Under
Over
Under
24rps
24rps
01-08
Dry
Minimum
Maximum
18rps
26rps
16rps
24rps
Time
6
Frequency
101rps
110rps
101rps
110rps
Time
6
410sec
37°F (3°C)
45°F (7°C)
Over
Under
Over
18rps
37°F (3°C)
45°F (7°C)
Over
Under
Over
18rps
104°F (40°C)
Under
Over
16rps
16rps
104°F (40°C)
Under
Over
16rps
16rps