Fujitsu AGU12RLF Service Instruction page 52

Hide thumbs Also See for AGU12RLF:
Table of Contents

Advertisement

Trouble shooting 22
Outdoor Unit - No Power
Check Point 1 : Check Installation Condition
Isn't the breaker down?
Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring
to Installation Manual or Data & Technical Manual.
OK
OK
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OK
OK
Check Point 3 : Check Electrical Components
Check the voltage of power supply.
>> Check if AC187 - 253V appears at Outdoor Unit Terminal L - N.
YES
YES
Check Fuse in Main PCB.
>> If Fuse is open, check if the wiring between Terminal and Main PCB is loose,
and replace Fuse.
Check Varistor in Main PCB.
>> If Varistor is defective, there is a possibility of an abnormal power supply.
Check the correct power supply and replace Varistor.
Upon checking the normal power supply, replace Varistor.
OK
If the symptom does not change by above Check 3, replace Main PCB.
Forecast of Cause:
1. Power supply failure
3. Electrical Components defective
02-27
2. External cause

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Agu9rlfAgu15rlfAou9rlffAou12rlffAou15rlff

Table of Contents