Information: Controller – View and Change Parameters and Alarm Severity
View and change system parameters and alarm severity from the factory defaults via:
A. Front Display - if equipped
B. LAN port in Local mode via a laptop (web pages)
C. LAN port in Network mode (web pages)
D. Craft Port via laptop and EasyView2 software or HyperTerminal.

Information: Rectifier Options

Rectifiers
single phase, hot-pluggable, fan - cooled
150027894
EP0500-UTEZ: 540W
CC109165602
EP1000-UTEZ: 1000W
CC109165610
EP1600-UTEZ: 1600W
1
Output Current at 54.5V. Outputs are power limited, not current limited.

Information: Alarm Connections

See the Slimline Power System Brochure for details.
Alarm connections are on the rear of the shelf - J1 is Alarm Outputs and J2 is Alarm Inputs.
Change alarm descriptions via LAN port (Web pages) or Craft port (EasyView2) when required.
Connector
Controller
Pin
1
2
3
4
5
6
7
8
9
10
1
Only with 6 relay controllers (...6R...).
2
Returns for R1 and R4 are bridged. Other returns are isolated.
Page 10
2023 ABB. All rights reserved.
100-120
200-240
100-120
200-240
100-120
200-240
J1 - Controller Variants
0I5R_D (5 Relays)
0I6R_DS (6Relays)
3 Inputs, 3 Relays
Output: R3 = Rtn
Input: PBT/TR
Output: R2 = Rtn
Input: Hi Ext. Temp.
2
Output: R1 = Rtn
Output: R1 = Rtn
Output: PMN Rtn
Output: PMN Rtn
Output: PMJ Rtn
Output: PMJ Rtn
Output: R3 = ACF
Input: RTNS
Output: R2 = RFA
Input: Cust. Alrm 1
Output: R1 = BD
Output: R1 = BD
Output: PMN
Output: PMN
Output: PMJ
Output: PMJ
SPS Shelf L051C_L052C_QSG
Recommended
Input
AC Breaker
V
A
A
AC
6.5
10
3.3
10
12
15
6
10
15
20
7.5
10
3C3R
9C0R_USB
9 Inputs, no Relays
Input: Door Open
Input: Surge Protect Fail
Input: Door 2 Open
Input: Ext DC Fail Major
Input: Ext DC Fail Minor
Input: Returns
Input: Retrieve Generator
Input: Battery Fail
Input: Air Conditioner Fail
Input: External Fan Fail
Output
Float V
W
DC
48-58
540
48-58
540
48-58
1000
48-58
1000
48-58
1200
48-58
1600
J2 - All Controllers
All
Input: SPD Fail
Input: AUX MAJ
Input: Air Cond. Fail
Input: Door Open
-48V
-48V
-48V
Output: R4 = FAJ
Output: R4 = Rtn
A
1
10
10
20
20
24
32
1
1,2
Rev 5.0