LG PQNFB17C0 Installation & Owner's Manual page 63

Table of Contents

Advertisement

Remarks
• Point NO. 1
1. The command executed is transmitted to the indoor unit regardless of the status of the indoor unit.
2. Present_Value property will not be used if a property has never been set in the past.
• Point NO. 7
1. The Present_Value property will be set to "1: Cool" as the default value if property has never
been set in the past.
2. The indoor unit will ignore the command to an object that does not have right to select operation
mode. Therefore, the controlled/monitored system must not use this object for the indoor unit
without the right to select operation mode.
• Point NO. 11
1. The indoor unit will disregard the command which the object which can't select the operation
mode. Therefore, controlled/monitored system shouldn't use the object which can't select the
operation mode.
• Point NO. 12
1. Present_value property will be set to "1:Low" as the default result if the property has not been set
in the past.
• Point NO. 13
1. The approximate set temperature range is 18 ~ 35 °C.
2. When COV registration is made, the COV will be reported the moment a temperature change of
at least 0.5 °C is detected.
• Point NO. 14/ 19
1. This object reports the room temperature data measured by the indoor units.
• Point NO. 16
1. This object's error code descriptions should be referred to the corresponding table at the
"Reference LG original Error Code".
• Point NO. 35 ~ 49
1. This objects are effective, in case 2Set Auto Mode of environment setting is enabled.
FUNCTIONAL SPECIFICATIONS ACP BACnet
53

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cqnfb17c0Pqnfb17c1Pqnfb17c2

Table of Contents