Line Differential Protection L4Cpdif; Possible Configurations - Hitachi 670 Series Application Manual

Hide thumbs Also See for 670 Series:
Table of Contents

Advertisement

1MRK505382-UEN Rev. K
IED
IEC15000451 V2 EN-US
Figure 30:
4.6.2

Line differential protection L4CPDIF

4.6.2.1

Possible configurations

The simplest and most common configuration is the protection of a conventional two-end power line
(see Figure 31). Circuit breakers (CBs) at both ends can be included in the protected zone
depending on their positions relative to the current transformers (CTs).
IED
IEC05000039 V3 EN-US
Figure 31:
It is also possible to protect a two-end power line that has two CB and CT groups at one end and one
CB and CT group at the other end (see Figure 32). All currents from the three CTs must be fed
separately to L4CPDIF which processes the measured currents independently from each other.
Summing up the CTs' secondary currents at the end with two CB and CT groups is not allowed. CBs
at both ends can be included in the protected zone depending on their positions relative to the CTs.
IEC15000459 V1 EN-US
Figure 32:
If there are two CB and CT groups at both ends of a two-end power line, information on currents
must be fed to all four current inputs of both IEDs. Current values at the remote end are obtained via
a communication channel as shown in Figure 33. Summing up the CTs' secondary currents at the
end with two CB and CT groups is not allowed. CBs at both ends can be included in the protected
zone depending on their positions relative to the CTs.
Communication set-up, 670/650 series
Application Guide
A
One three–winding transformer in the protected zone
Communication channel
Two-end power line with one CB and one CT group at each end
Two-end power line with two CB and CT groups at one end
© 2017 - 2023 Hitachi Energy. All rights reserved
Analog and binary signal transfer for line differential protection
Protected zone
T
T
Protected zone
IEC15000459-1-en.vsd
B
IED
IEC15000451-2-en.vsdx
GUID-566BF5F0-3E2D-42D8-9D53-BCAFB7F0BEA9 v3
IED
IEC05000039-3-en.vsd
Section 4
31

Advertisement

Table of Contents
loading

This manual is also suitable for:

650 series

Table of Contents