Selecting The Installation Site; Indoor Unit; How To Install The Indoor Unit; (Y1 Type) - Panasonic S-22MU1E5 Installation Instructions Manual

Vrf system air conditioner
Hide thumbs Also See for S-22MU1E5:
Table of Contents

Advertisement

2. SELECTING THE INSTALLATION SITE

2-1. Indoor Unit

AVOID:
● areas where leakage of flammable gas may be expected.
● places where large amounts of oil mist exist.
● direct sunlight.
● locations near heat sources which may affect the
performance of the unit.
● locations where external air may enter the room directly.
This may cause "condensation" on the air discharge ports,
causing them to spray or drip water.
● locations where the remote controller will be splashed with
water or affected by dampness or humidity.
● installing the remote controller behind curtains or furniture.
● locations where high-frequency emissions are generated.
DO:
● select an appropriate position from which every corner of the
room can be uniformly cooled.
● select a location where the ceiling is strong enough to
support the weight of the unit.
● select a location where tubing and drain pipe have the
shortest run to the outdoor unit.
● allow room for operation and maintenance as well as
unrestricted air flow around the unit.
● install the unit within the maximum elevation difference
above or below the outdoor unit and within a total tubing
length (L) from the outdoor unit as detailed in the installation
manual packed with the outdoor unit.
● allow room for mounting the remote controller about 1m off
the floor, in an area that is not in direct sunlight or in the flow
of cool air from the indoor unit.
NOTE
Air delivery will be degraded if the distance from the floor to the ceiling is
greater than 3 m.
min. 25 cm
Font view
NOTE
The rear of the indoor unit can be installed flush against
the wall.
Air
discharge
min. 50 cm
Ceiling
Ceiling
Wall
min. 25 cm
Air intake
Side view
Max. 25 cm
Obstacle
min. 1 m
Low Silhouette Ducted, Slim Low Static Ducted, High
Static Pressure Ducted, 4-Way Cassette 60x60
25 cm
25 cm

3. HOW TO INSTALL THE INDOOR UNIT

■ 4-Way Cassette 60x60 Type

(Y1 Type)

3-1. Preparation for Ceiling Suspension

This unit uses a drain pump. Use a carpenter's level to check
that the unit is level.

3-2. Mounting the Suspension Bolts

(1) Fix the suspension bolts securely to the ceiling using the
method shown in the diagrams (Figs. 3-1 and 3-2), by
attaching them to the ceiling support structure, or by any
other method that ensures that the unit will be securely and
safely suspended.
(2) Follow the diagram to make the holes in the ceiling. (Refer
to Fig. 3-2)
Fig. 2-1
9
4-Way Cassette Type
1 m
1 m
1 m
1 m
1 m
indoor unit
Ceiling
min. 3 m
Fig. 2-2
25 cm
1 m
Concrete
Hole-in-anchor
Hole-in-plug
Suspension bolt (M10 or 3/8")
(field supply)
indoor unit
Obstacles
1 m
1 m
1 m
1 m
Fig. 2-3
Insert
Fig. 3-1