Finishing The Installation; How To Install The Timer Remote Controller; (Optional Part); Not E - Panasonic S-22MU1E5 Installation Instructions Manual

Vrf system air conditioner
Hide thumbs Also See for S-22MU1E5:
Table of Contents

Advertisement

5-5. Finishing the Installation

After finishing insulating and taping over the tubing, use sealing
putty to seal off the hole in the wall to prevent rain and draft
from entering. (Fig. 5-10)
Apply putty here
6. HOW TO INSTALL THE TIMER REMOTE
CONTROLLER (OPTIONAL PART)

NOT E

Refer to the Operating Instructions attached to the optional

Timer Remote Control Unit.

7. HOW TO INSTALL THE CEILING PANEL

■ 4-Way Cassette Type (U1 Type)

Accessories
Ceiling panel ×1

7-1. Preparation for Ceiling Panel Installation

(1) Checking the unit position
1) Check that the ceiling hole is within this range:
860 mm × 860 mm to 910 mm × 910 mm
2) Confirm that the position of the indoor unit and the
ceiling as shown in the diagram. If the positions of
the ceiling surface and unit do not match, air leakage,
water leakage, flap operation failure, or other problems
may occur.
CAUTION
Never place the panel face-down.
Either hang it vertically or place it on top of
a projecting object. Placing it face-down will
damage the surface.
Do not touch the flap or apply force to it.
(This may cause flap malfunction.)
Tubing
Fig.5-10
Washer head screws ×4
M5 × 40
ø18
Installation notes ×1
A
Ceiling side
A
: Be sure to necessarily make a space within the range of
12 mm - 17 mm.
If not within this range, malfunction or other trouble may
occur.
Flap
44
Screws ×4
4 × 12
Main unit
Ceiling opening
dimension

Advertisement

Table of Contents
loading