13.6 Protection Functions

Outdoor coil temperature protection (T3)
i. If T3 > 143.6°F, compressor is de-energized.
ii. If T3 < 129.2°F, compressor is energized.
Ambient temperature protection (T4)
i. If 23°F ≤ T4 < 125°F, unit can operate in cooling.
ii. If ‒4°F ≤ T4 < 86°F, unit can operate in heating.
iii. If T4 < ‒4°F, heat pump will provide 24V control to indoor unit
energizing electric heat (if installed).
See Product Specifi cation for extended performance data.
Discharge Temperature (DT) protection (T5)
i. If DT > 230°F during cooling mode, the compressor will stop.
ii. If DT < 212°F during cooling mode, the compressor will restart.
iii. If DT > 230°F during heating mode, the compressor will stop.
iv. If DT < 212°F during heating mode, the compressor will restart.
High Pressure (HP) protection (mechanical open/close pressure
switch)
i. High Pressure Switch opens at P > 580 PSIG, the compressor
and outdoor fan stop.
ii. High Pressure Switch closes at P < 435 PSIG, the compressor
and outdoor fan restart.
Low Pressure (LP) protection
i. If Low Pressure < 43.5 PSI for 5 minutes during cooling mode,
the compressor and outdoor fan will stop.The system will attempt to
run again after 6 minutes.
ii. If condensing temp. Tc < outdoor ambient temp. T4 during
heating mode, the compressor and outdoor fan will stop.
Module (inverter) protection (TF)
i. If TF > 172°F, the compressor and outdoor fan will stop.
ii. If TF < 160°F, the compressor and outdoor fan will restart.
2 4 |