Error Code Troubleshooting (Odu) - Bosch IDP Premium 18 SEER2 Series Installation Instructions Manual

Inverter ducted packaged heat pump
Table of Contents

Advertisement

13.10 Error Code Troubleshooting (ODU)

Error Code
Description (Sensor)
P1
High pressure switch (HPS) protection
P5
Condenser coil temperature (T3) protection in cooling
P3
Compressor over current protection
Table 22
P1 (High pressure switch (HPS) protection)
Diagnosis
Check whether the high
pressure switch wires
are seated normally
Yes
Check whether high pressure
switch is closed
Yes
Check whether indoor and
outdoor units are normal by
filter and airflow
Yes
Cooling mode refers to P5
Figure 34
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump - BTC 761703103 A (11.2022)
Handling
No
Reseat the wires according
to wiring diagram
No
Replace high pressure switch
No
Exclude all fault reasons
and restart
P5 (Condenser coil temperature (T3) protection in cooling)
Diagnosis
Check whether T3 is normal
according to Table 34 (between
temperature and resistance)
Yes
Check whether outdoor unit
motor is abnormal or whether
the outdoor condenser coil is
blocked
No
Check whether there is short
circuit in air outlet and inlet side
No
Check whether the charge is
correct by subcooling
according to installation guide
in charge mode when cooling
Yes
Check whether there is
normal throttle
Yes
Figure 35
P3 (Compressor over current protection)
Diagnosis
Check whether outdoor unit
motor is abnormal and the
outdoor condenser coil is
blocked
No
Check whether compressor
wiring is normal
Yes
Check whether compressor
insulation resistance is greater
than 100KΩ
Yes
Restart system and check whether
the difference of high and low
pressure is more than 30 PSI after
compressor has run for 10 mins
Yes
Check whether the
compressor current is more
than 15A for 2/3 ton when
protected
Yes
Figure 36
Installation Instructions
Handling
No
Replace the T3 sensor
Replace the fan or
Yes
remove all the blockage
Yes
Do something to avoid air
return short circuit
No
Adjust refrigerant charge
No
Adjust or repair the EEV
throttle
Handling
Replace the fan or
Yes
remove all the barriers
No
Wire correctly according to
the wiring diagram
No
Replace the compressor
No
Replac
e the compressor
No
Replace the board
Replace the compressor
| 29

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Brba-36hwd1n1-m18

Table of Contents