LM Split CS Series Heat Pump
Liquid Line Charge per Linear Foot
LIQUID LINE
SIZE, O.D.
R410A OZ
PER FOOT
Table 3 Liquid Line Charge per Linear Foot
Additional Adjustments Required when Pairing LM Split CS with BVA2.0 and BMAC
1. Adjust factory charge as per Table #4 or Table
#5, and then proceed with additional charge
adjustment calculations by line size as per
Table #2.
2. Adjust TXV as per Table #6 or Table #7, as
Charge Adjustments (oz) for LM Split CS when Paired with BOSCH BVA2.0
BVA-24WN1-M20
CS MODEL
LM024-1CSC
LM024-1CSN
LM036-1CSC
LM036-1CSN
LM048-1CSC
LM048-1CSN
LM060-1CSC
LM060-1CSN
Table 4 Charge Adjustments (oz) for LM Split CS when Paired with BOSCH BVA2.0
LM Split CS Series Heat Pump
1/4
5/16
.25
.44
BVA-36WN1-M20
-6
-9
Subject to change without prior notice
3/8
.60
appropriate.
3. Adjust BVA motor setting as per Table #8 to
obtain the rated airflow. Refer to the BVA2.0
operational manual for additional airflow
settings.
Air Handler Model
BVA-48WN1-M20
0
0
13
Refrigerant Lines | 11
1/2
1.15
BVA-60WN1-M20
8
8733827906 (2021/11)
5/8
1.95
0
0