30 | Troubleshooting
SmartStart Assist Troubleshooting
Red Led
Relay
Contact*
FULLY ON +
11/12
2 FLASHES
11/14
3 FLASHES
11/14
4 FLASHES
11/14
5 FLASHES
11/14
N/A
11/12
N/A
11/12
N/A
11/12
N/A
11/12
Green Led
Relay
Contact*
FLASHING
11/12
FULLY ON
11/12
+ APPLICABLE TO RSBS2332A2V.2C24HP. FOR MODELS,NO INDICATION ON THE RED LED IS PROVIDED
****REFER TO VOLTAGE DIPS AND INTERRUPTIONS SECTION FOR MODE OF OPERATION OF THE SSA IOM
Table 14 SmartStart Assist Troubleshooting
SmartStart Assist Flashing Sequence
Fig. 14 SmartStart Assist Flashing Sequence
During recovery from an alarm condition, the red LED will flash at twice the normal flashing frequency
between successive flashing cycles as shown above to indicate that the SmartStart Assist is in recovery
mode, which lasts for five minutes.
8733827906 (2021/11)
Condition
Min. recovery time between starts
and/or recovery time between stop to
start
Undervoltage (Ue<190VAC)
Overcurrent (>80A for >1 sec.)
relay protection
incomplete ramp
Supply phase loss
Idle state
Ramping state
Bypass mode
Condition
Power supply alarm
Idle State
*APPLIES ONLY TO RSB23XXA2V22C24..MODELS
**MONITORED DURING IDLE AND BYPASS
***REFER TO NOTE 6 IN MODE OF OPERATION SECTION OF THE SSA IOM
Subject to change without prior notice
LM Split CS Series Heat Pump
Action
Auto reset when minimum recovery
time elapses
Auto reset with 5 mins. recovery **
Auto reset with 5 mins. recovery
Auto reset with 5 mins. recovery***
Auto reset with 5 mins. recovery
Physical check
Action
Replace SmartStart device
RSBS waiting for control signal to
start
LM Split CS Series Heat Pump