Technical specifications
Article number
Power
Infeed power to the backplane bus
Power consumption from the backplane bus (bal-
anced)
Power loss
Power loss, typ.
Memory
Number of slots for SIMATIC memory card
SIMATIC memory card required
Work memory
•
•
Load memory
•
Backup
•
CPU processing times
for bit operations, typ.
for word operations, typ.
for fixed point arithmetic, typ.
for floating point arithmetic, typ.
CPU-blocks
Number of elements (total)
DB
•
•
FB
•
•
FC
•
•
44
integrated (for program)
integrated (for data)
Plug-in (SIMATIC Memory Card), max.
maintenance-free
Number range
Size, max.
Number range
Size, max.
Number range
Size, max.
6ES7513-1AM03-0AB0
10 W
5.5 W
3.4 W
1
Yes
600 kbyte
2.5 Mbyte
32 Gbyte
Yes
25 ns
32 ns
42 ns
170 ns
4 000; Blocks (OB, FB, FC, DB) and UDTs
1 ... 60 999; subdivided into: number range that
can be used by the user: 1 ... 59 999, and number
range of DBs created via SFC 86: 60 000 ... 60 999
2.5 Mbyte; For DBs with absolute addressing, the
max. size is 64 KB
0 ... 65 535
600 kbyte
0 ... 65 535
600 kbyte
CPU 1513-1 PN (6ES7513-1AM03-0AB0)
Equipment Manual, 11/2023, A5E40881673-AD