Technical specifications
Article number
PROFINET IO Controller
Services
Update time for IRT
Update time for RT
48
–
Isochronous mode
–
Direct data exchange
–
IRT
–
PROFIenergy
–
Prioritized startup
–
Number of connectable IO Devices, max.
–
Of which IO devices with IRT, max.
–
Number of connectable IO Devices for RT,
max.
–
of which in line, max.
–
Number of IO Devices that can be simulta-
neously activated/deactivated, max.
–
Number of IO Devices per tool, max.
–
Updating times
–
PROFINET Security Class
–
for send cycle of 250 µs
–
for send cycle of 500 µs
–
for send cycle of 1 ms
–
for send cycle of 2 ms
–
for send cycle of 4 ms
–
With IRT and parameterization of "odd"
send cycles
–
for send cycle of 250 µs
–
for send cycle of 500 µs
–
for send cycle of 1 ms
–
for send cycle of 2 ms
–
for send cycle of 4 ms
6ES7513-1AM03-0AB0
Yes
Yes; Requirement: IRT and isochronous mode
(MRPD optional)
Yes
Yes; per user program
Yes; Max. 32 PROFINET devices
128; In total, up to 512 distributed I/O devices can
be connected via AS-i, PROFIBUS or PROFINET
64
128
128
8; in total across all interfaces
8
The minimum value of the update time also de-
pends on communication share set for PROFINET
IO, on the number of IO devices, and on the
quantity of configured user data
1
250 μs to 4 ms; Note: In the case of IRT with
isochronous mode, the minimum update time of
500 µs of the isochronous OB is decisive
500 µs to 8 ms
1 ms to 16 ms
2 ms to 32 ms
4 ms to 64 ms
Update time = set "odd" send clock (any multiple
of 125 µs: 375 µs, 625 µs ... 3 875 µs)
250 µs to 128 ms
500 µs to 256 ms
1 ms to 512 ms
2 ms to 512 ms
4 ms to 512 ms
CPU 1513-1 PN (6ES7513-1AM03-0AB0)
Equipment Manual, 11/2023, A5E40881673-AD