Installation

8
Installation
8.1

Place of installation

Note!
Ambient conditions!
In the event that the chiller is not installed under suitable ambient conditions, the ability of the device to
condense refrigerant gas is impaired. This can result in a higher load of the refrigerating compressor, and
in a loss of efficiency and performance of the chiller.
This in turn leads to overheated condenser fan motors, to malfunction of electric components and to a
breakdown of the chiller. Failures of this type will affect warranty considerations.
Do not install the chiller in an environment in which chemicals with a corrosive effect, explosive gases,
toxic gases, evaporation heat, high ambient temperatures or extreme dust and dirt can be found.
Minimum installation requirements:
Choose an area which is clean and dry, free from dust and protected against atmospheric disturbances.
The load-bearing zone must be even, horizontal and able to bear the weight of the chiller.
Minimum ambient temperature +1°C.
Maximum ambient temperature +50°C.
Ensure a proper cooling air replacement.
Allow a sufficient clearance on each side of the chiller for proper ventilation and to facilitate maintenance operations.
The chiller does not require attachment to the floor surface.
Do not obstruct the ventilation grille (not even partially).
Prevent any recirculation of the outgoing cooling air.
Protect the chiller against draughts.