Refrigerating Compressor; Condenser (Air-Cooled); Condenser (Water-Cooled); Cooling-Water Regulating Valve - Beko BEKOBLIZZ LC 480 Instructions For Installation And Operation Manual

Compressed air refrigeration chiller
Table of Contents

Advertisement

Technical description

11.5 Refrigerating compressor

The employed refrigerating compressors are constructed by leading manufacturers. The hermetically sealed
construction is absolutely gastight. The integrated safeguard protects the compressor against overheating and excess
current. The protection is automatically reset as soon as the nominal conditions are reached again.

11.6 Condenser (air-cooled)

The condenser is the component in which the gas coming from the compressor is cooled down, condensed and
liquefied. Under no circumstances must the temperature of the ambient air exceed the nominal values. It is also
important that the condenser unit is kept free from dust and other impurities.

11.7 Condenser (water-cooled)

The condenser is the component in which the gas coming from the compressor is cooled-down, condensed and
liquefied.
The water inlet temperature must not exceed the nominal values. Likewise, a correct flow must be ensured. The water
entering the condenser must be free from impurities.

11.8 Cooling-water regulating valve

The cooling-water controller serves to keep the condensation pressure or the condensation temperature constant
during water cooling. When the chiller is switched off, the valve automatically blocks the cooling-water flow.

11.9 Filter dryer

Despite controlled vacuuming, traces of moisture can accumulate in the refrigeration cycle. The filter dryer serves to
absorb this moisture and to bond it.

11.10 Capillary tube

The capillary tube is a copper tube with a reduced diameter which is located between the condenser and the
evaporator, serving as a restrictor to reduce the pressure of the refrigerant. The pressure reduction serves to reach an
optimum temperature inside of the evaporator. The lower the outlet pressure at the capillary tube, the lower the
evaporation temperature.
The length and the inner diameter of the capillary tube are exactly dimensioned to ensure the performance of the
chiller. Settings or maintenance works are not required.

11.11 Air-to-refrigerant heat exchanger

Also called evaporator. The liquid formed in the condenser is evaporated in this part of the circuit. In the evaporation
phase the refrigerant tends to absorb the heat from the compressed air present in the other side of the exchanger.
Refrigerant and air are in counter flow, thus contributing to limit pressure drop and to provide efficient thermal
exchange.

11.12 Condensate separator

The cold air exiting the evaporator goes through the hi-efficiency condensate separator featuring a stainless steel
mesh. As the condensate transported by the air gets in contact with the mesh net it is separated and expelled by
means of the draining device. The resulting cold and dry air is then conveyed into chiller outlet.
The mesh type mist separator offers the benefit to be highly efficient even with variable flow rates.

11.13 Hot-gas bypass valve

At partial load, the valve directly returns a part of the hot gas to the suction line of the refrigerating compressor. The
evaporation temperature and the evaporation pressure remain constant.
BEKOBLIZZ® LC 480-720
27

Advertisement

Table of Contents
loading

Table of Contents