Hitachi AF-BCK-01 Installation And Operation Manual page 15

Boiler combination kit
Table of Contents

Advertisement

Available languages

Available languages

6.4. COmmON WIRING
CAUTION:
All the field wiring and electrical components must comply with local codes.
6.4.1. ELECTRICAL WIRING bETWEEN AQUAFREE
AND bOILER COmbINATION kIT.
Connect the electrical wires between the AquaFREE, the Boiler
Combination Kit and the Boiler, as shown in the next diagram.
Follow local codes and regulations when performing electrical wiring.
Use twist pair wire (more than 0.75 mm²) for operation wiring
between AquaFREE and Boiler Combination Kit.
Use 2-core wire for the operating line (Do not use wire with more
than 3 cores).
Use shielded wires for intermediate wiring to protect the units from
noise obstacle at length of less than 300m and size complied with
local code.
Single phase connection:
Boiler
Electrical connections
The recommended breaker sizes are shown in Table of electrical
data and recommended Wiring, Breaker
Size/1 O.U.
In the case that a conduit tube for field-wiring is not used, fix rubber
bushes with adhesive on the panel.
All the field wiring and equipment must comply with local and
international codes.
Indoor unit (AquaFREE)
BCK
15
Outdoor Unit