CHAPTER 7: CONNECTING FIELD WIRING TO THE D20E MODULE
D20E-K control outputs module
D20E ETHERNET I/O MODULE INSTRUCTION MANUAL
The D20E-K has 34 on-board relays that are factory configured into a variety of output
types; see Table 22 for connection details.
The W1, W2 to W5, and W7-W34 jumpers are located on the D20E-K as shown in Figure 17.
Figure 17: D20E-K module - jumper locations
Jumper
Jumper
W1
W6
W2 to W5
See Table 23 for terminal block connection details.
Table 22: D20E-K - summary of control types and jumper setting positions
Control Type
Trip/Close
Trip/Close supply: TB2-54(+/‒) and TB2-1(‒/+)
Jumper W1: 1 & 4, 2 & 3
DPST
DPST supply: TB2-54(+/‒) and TB2-1(‒/+)
Jumper W1: 1 and 2
Form C
REMOTE/LOCAL switch supply: TB2-54(+) and
TB2-1(‒)
Raise/Lower
Raise/Lower supply: TB2-54(+/‒) and TB2-1(‒/+)
Jumper W1: 1 & 2
See Table 24 (and Notes) for D20E-K (DB25) Interface jumper settings and terminal block
connections.
Jumpers
Jumpers
W10 to W14
Jumpers
Jumpers
W6 to W9
W15 to W18
Jumper and Supply
W2-W5, W7-W34
W6
W2-W5, W7-W34
W6
W2-W5, W7-W34
W2-W5, W7-W34
W6
GE INFORMATION
Jumpers
Jumpers
W19 to W22
W27 to W30
Jumpers
Jumpers
W31 to W34
W23 to W26
Setting
89