Error Code [7101] - Mitsubishi Electric PUHY-HP200YNW-A Service Handbook

Advertisement

[7-9 Error Code Definitions and Solutions: Codes [7000 - 7999] ]
7-9-2

Error Code [7101]

1. Error code definition
Capacity code setting error
2. Error definition and error detection method
Connection of incompatible (wrong capacity code) indoor unit or outdoor unit
3. Error source, cause, check method and remedy
After troubleshooting the error using the check methods and remedies shown below, turn the power back on.
Error source
Outdoor unit
(1) The model name (capacity code) set by the
Indoor unit
switch (SW2) is wrong.
*The capacity of the indoor unit can be con-
firmed by the self-diagnosis function (SW1
operation) of the outdoor unit.
Outdoor unit
(2) The model selection switches (SW5-3 - 5-8)
on the outdoor unit are set incorrectly.
HP200 model
HP250 model
BS_07_L
Cause
SW5
Model
3
4
5
6
OFF
ON
ON
OFF
OFF
ON ON
ON OFF OFF
Check method and remedy
1) Check the model name (capacity code) of the in-
door unit which has the error source address set
by the switch (SW2 on indoor unit board).
When the model name set by the switch is differ-
ent from that of the unit connected, turn off the
power source of the outdoor and the indoor units,
and change the setting of the capacity code.
Check the setting for the model selection switch
on the outdoor unit (Dipswitches SW5-3 - 5-8 on
the outdoor unit control board).
7
8
ON
OFF
ON
65
chapter 7 -