[2-10 Restrictions on Refrigerant Pipes ]

2-10 Restrictions on Refrigerant Pipes

2-10-1

Restrictions on Refrigerant Pipe Length

(1) HP200, 250YNW models
Outdoor unit
A
First branch
(Branch joint)
Branch joint
Length
Total pipe length
Total pipe length (L) from the outdoor unit to the
farthest indoor unit
Total pipe length from the first branch to the far-
thest indoor unit ( )
Height
Between indoor and
difference
outdoor units
Between indoor units
*1. If the piping length exceeds 40 meters (but does not exceed 90 meters), use one-size larger pipes for all the liquid
pipes beyond 40 meters. In the figure above, the pipes whose size should be increased by one size are indicated
by "C," "b," and "c" when the piping length exceeds 40 meters at point C.
*2. If the vertical difference between indoor units exceeds 15 meters (but does not exceed 30 meters), use one-size
larger liquid pipes for piping between the first branch and the relevant indoor units. In the figure above, the pipes
whose size should be increased by one size are indicated by "B," "C," "a," "b," and "c" when the "h" exceeds 15
meters.
26
- chapter 2
D
L
B
C
a
b
1
Indoor
2
Indoor
3
Operation
Outdoor unit above in-
door unit
Outdoor unit below in-
door unit
d
Indoor
4
c
Indoor
Pipe sections
A+B+C+D
+a+b+c+d+e+f
A+B+C+c or
A+D+f
B+C+c or
D+f
H
H'
h
Branch header
cap
e
f
Indoor
Indoor
6
5
Unit: m [ft]
Allowable length of
pipes
1000 [3280] or less
165 [541] or less
(Equivalent length 190
[623] or less)
*1
40 [131] or less
50 [164] or less
40 [131] or less
*2
15 [49] or less
BS_02_M

Advertisement

loading