Advertisement

Quick Links

AIR CONDITIONER
Wall mounted type
DESIGN & TECHNICAL MANUAL
INDOOR
OUTDOOR
ASBG09CMBA
ASBG12CMBA
AOBG09CMCA
AOBG12CMCA
DR_AS191EF_01
2023.02.16

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu ASBG09CMBA

  • Page 1 AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASBG09CMBA ASBG12CMBA OUTDOOR AOBG09CMCA AOBG12CMCA DR_AS191EF_01 2023.02.16...
  • Page 2 • Product specifications and design are subject to change without notice for future improvement. • For further details, please check with our authorized dealer. Trademarks ™ FGLair is trademark of Fujitsu General Limited in the United States, other countries or both. ™ Google Play is trademark of Google LLC. ®...
  • Page 3: Table Of Contents

    CONTENTS Part 1. INDOOR UNIT................1 1. Specifications....................2 2. Dimensions....................3 2-1. Models: ASBG09CMBA and ASBG12CMBA..............3 3. Wiring diagrams ....................5 3-1. Models: ASBG09CMBA and ASBG12CMBA..............5 4. Capacity table....................6 4-1. Cooling capacity.......................6 5. Fan performance ...................7 5-1. Air velocity distributions....................7 5-2. Airflow ..........................9 6.
  • Page 4 CONTENTS (continued) Part 2. OUTDOOR UNIT..............29 1. Specifications....................30 2. Dimensions....................31 2-1. Models: AOBG09CMCA and AOBG12CMCA..............31 3. Installation space ..................32 3-1. Models: AOBG09CMCA and AOBG12CMCA..............32 4. Refrigerant circuit ..................35 4-1. Model: AOBG09CMCA ....................35 4-2. Model: AOBG12CMCA ....................36 5. Wiring diagrams ..................37 5-1.
  • Page 5: Part 1. Indoor Unit

    Part 1. INDOOR UNIT WALL MOUNTED TYPE: ASBG09CMBA ASBG12CMBA...
  • Page 6: Specifications

    1. Specifications Wall mounted Type Inverter, Cooling only Model name ASBG09CMBA ASBG12CMBA Power supply 220 V~ 60 Hz Power supply intake Outdoor unit Available voltage range 198—242 V 2.64 3.52 Rated Btu/h 9,000 12,000 Capacity 0.9—3.2 0.9—3.8 Min.—Max. Btu/h 3,100—10,900 3,100—13,000...
  • Page 7: Dimensions

    2. Dimensions 2-1. Models: ASBG09CMBA and ASBG12CMBA Unit: mm Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 3 - 2-1. Models: ASBG09CMBA and ASBG12CMBA 2. Dimensions...
  • Page 8 ¢ Installation space requirement Provide sufficient installation space for product safety. Unit: mm Outline of unit 25 or more 52 or more 70 or more 130 or more 1,500 or more - 4 - 2-1. Models: ASBG09CMBA and ASBG12CMBA 2. Dimensions...
  • Page 9: Wiring Diagrams

    3. Wiring diagrams 3-1. Models: ASBG09CMBA and ASBG12CMBA - 5 - 3-1. Models: ASBG09CMBA and ASBG12CMBA 3. Wiring diagrams...
  • Page 10: Capacity Table

    Capacity tables show each of following values calculated based on the outdoor temperature and the indoor temperature, under given Airflow Rate (AFR): For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) 4-1. Cooling capacity ¢ Model: ASBG09CMBA Indoor temperature °CDB °CWB °CDB...
  • Page 11: Fan Performance

    5. Fan performance 5-1. Air velocity distributions ¢ Model: ASBG09CMBA Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s...
  • Page 12 ¢ Model: ASBG12CMBA Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center Unit: m/s Side view Horizontal louver: Down...
  • Page 13: Airflow

    5-2. Airflow ¢ Model: ASBG09CMBA  Cooling Fan speed Airflow HIGH QUIET ¢ Model: ASBG12CMBA  Cooling Fan speed Airflow HIGH QUIET - 9 - 5-2. Airflow 5. Fan performance...
  • Page 14: Operation Noise (Sound Pressure)

    6. Operation noise (sound pressure) 6-1. Noise level curve ¢ Model: ASBG09CMBA  Cooling NC-65 NC-60 NC-55 NC-50 HIGH NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 NC-15 QUIET 2,000 4,000 8,000 1,000 Octave band center frequency, Hz ¢ Model: ASBG12CMBA  Cooling...
  • Page 15: Sound Level Check Point

    6-2. Sound level check point Microphone Microphone NOTE: Detailed shape of the actual indoor unit might be slightly different from the one illustrated above. - 11 - 6-2. Sound level check point 6. Operation noise (sound pressure)
  • Page 16: Safety Devices

    7. Safety devices Model Type of Protection form protection ASBG09CMBA ASBG12CMBA Circuit protection Current fuse (PCB*) 250 V, 3.15 A °C Activate Fan motor stop Fan motor Thermal protector protection program °C Reset Fan motor restart *PCB: Printed Circuit Board - 12 - 7.
  • Page 17: External Input And Output

    8. External input and output With using external input and output functions, this product can be operated inter-connectedly with an external device. Connector Input Output Remarks CNA01 Control input — See external input/output CNB01 — Operation status output settings for details. CNB02 —...
  • Page 18 • When function setting is “Forced stop” mode: Input signal Forced stop Command Normal Operation Indoor unit Stop Remote controller Remote control operation invalidity • Optional part: Part name Model name Exterior External input wire External Connect Kit UTY-XWZXZ5 Communication Kit UTY-XCBXZ2 * For operating the external function, the wall mounted type requires the communication kit in addi- tion to the wire (UTY-XWZXZ5).
  • Page 19: External Output

    8-2. External output With using external output function, operating status of this product can be transmitted to the exter- nal device, and also, this product can be inter-connected with the external device. ¢ Operation status output Air conditioner operation status signal can be output. •...
  • Page 20 ¢ Error status output Air conditioner error status signal can be output. • Circuit diagram example: Indoor unit control PCB Communication kit Connected unit Connector DC 24 V Example: Relay unit Example: Display Relay power supply 10 m* Signal Optional parts Locally purchased –...
  • Page 21: Group Connection

    9. Group connection Wiring regulation on the remote controllers in the multi-split systems are reviewed and allowed for group connection. Example of group connection Indoor unit Indoor unit Outdoor unit Outdoor unit *Exterior of each device shown above might be different from the actual one. NOTES: •...
  • Page 22: Remote Controller Address Setting Procedure For Wireless Remote Controllers

    • Required parts for group connection – Optional part: Indoor unit type Communication Kit Wall mounted UTY-XCBXZ2 As for the optional parts, "Others" on page 28 – Service part: Wire with connector (Service part no. 9705932012) Wiring example for multiple remote control or group control: Crimping terminal and its insulation cap (Locally purchased) Remote controller cable (Locally purchased)
  • Page 23: Remote Controller

    10. Remote controller 10-1. Wireless remote controller ¢ Overview a MODE button b FAN SPEED button c POWERFUL button d ECONOMY button e ENERGY SAVING button f SLEEP button g OUTDOOR LOW NOISE button h CANCEL button i RESET button j TEST RUN button k SERVICE CHECK button l CLOCK ADJUST button...
  • Page 24 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 181 × 58 × 17 Weight 116 (without batteries)  Holder Unit: mm Top view Ø (Hole) Hole 26.3 62.8 Front view Side view Size (H ×...
  • Page 25: Function Settings

    11. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 11-1. Function settings by using remote controller Some function settings can be changed on the remote controller. After confirming the setting proce- dure and the content of each function setting, select appropriate functions for your installation envi- ronment.
  • Page 26 ¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected.  Function setting list Function no. Functions Remote controller address setting Filter sign...
  • Page 27 2) Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room. If the indication is not required, select "No indication" (03). Function number Setting value Setting description Factory setting...
  • Page 28 7) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description Factory setting Operation/Stop mode ♦ (Setting prohibited) Forced stop mode 8) Room temperature sensor switching (Aux.) To use the temperature sensor on the wired remote controller only, change the setting to "Wired re- mote controller"...
  • Page 29: 11-2.Custom Code Setting For Wireless Remote Controller

    11-2. Custom code setting for wireless remote controller To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required. NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the custom code.
  • Page 30: Accessories

    12. Accessories 12-1. Models: ASBG09CMBA and ASBG12CMBA Part name Exterior Part name Exterior Self-tapping screw Operation manual (large) Self-tapping screw Installation manual (small) Wall hook bracket Filter holder Remote controller Ion deodorization filter Remote controller Apple-catechin filter holder Cloth tape - 26 - 12-1.
  • Page 31: Optional Parts

    13. Optional parts 13-1. Controllers Exterior Part name Model name Summary Large and full-dot liquid crystal screen, wide and large keys easy to press, user-intuitive arrow key. Wired Remote Wire type: Polar 3-wire UTY-RVNYM Controller Optional Communication Kit is necessary for installation. Room temperature can be controlled by detecting the temperature accurately with thermo sensor.
  • Page 32: 13-2.Others

    13-2. Others Exterior Part name Model name Summary Required when external device is connected. External UTY-XWZXZ5 Connect Kit Use to connect with optional devices and air conditioner PCB. Communication UTY-XCBXZ2 Connecting point: CN2 on Main PCB Remotely manage an air conditioning system using mobile devices such as smartphones and tablets.
  • Page 33: Part 2. Outdoor Unit

    Part 2. OUTDOOR UNIT SINGLE TYPE: AOBG09CMCA AOBG12CMCA...
  • Page 34: Specifications

    1. Specifications Type Inverter, Cooling only Model name AOBG09CMCA AOBG12CMCA Power supply 220 V~ 60 Hz Power supply intake Outdoor unit Available voltage range 198—242 V Starting current Airflow rate 1,740 1,700 Type × Qty Propeller fan × 1 Motor output dB (A) Sound pressure level* Dimensions...
  • Page 35: Dimensions

    2. Dimensions 2-1. Models: AOBG09CMCA and AOBG12CMCA Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 31 - 2-1. Models: AOBG09CMCA and AOBG12CMCA 2.
  • Page 36: Installation Space

    3. Installation space 3-1. Models: AOBG09CMCA and AOBG12CMCA ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
  • Page 37  Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 4 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
  • Page 38  Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
  • Page 39: Refrigerant Circuit

    4. Refrigerant circuit 4-1. Model: AOBG09CMCA Heat exchanger 3-way 2-way (INDOOR) valve valve Strainer Expansion valve Heat exchanger Strainer (OUTDOOR) : Thermistor (Discharge temperature) : Thermistor (Outdoor temperature) : Thermistor (Pipe temperature) : Thermistor (Pipe temperature) : Thermistor (Room temperature) - 35 - 4-1.
  • Page 40: Model: Aobg12Cmca

    4-2. Model: AOBG12CMCA Heat exchanger 3-way 2-way (INDOOR) valve valve Muffler 4-way valve Strainer Expansion valve Heat exchanger Strainer (OUTDOOR) : Thermistor (Discharge temperature) : Thermistor (Outdoor temperature) : Thermistor (Heat exchanger out temperature) : Thermistor (Pipe temperature) : Thermistor (Room temperature) - 36 - 4-2.
  • Page 41: Wiring Diagrams

    5. Wiring diagrams 5-1. Models: AOBG09CMCA and AOBG12CMCA - 37 - 5-1. Models: AOBG09CMCA and AOBG12CMCA 5. Wiring diagrams...
  • Page 42: Capacity Compensation Rate For Pipe Length And Height Difference

    6. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 6-1. Model: AOBG09CMCA NOTE: Values mentioned in the table are calculated based on the maximum capacity.
  • Page 43: Additional Charge Calculation

    7. Additional charge calculation 7-1. Model: AOBG09CMCA Refrigerant type Factory charge amount ¢ Refrigerant charge Total pipe length 15 or less 20 (Max.) 20 g/m Additional charge amount 7-2. Model: AOBG12CMCA Refrigerant type Factory charge amount ¢ Refrigerant charge Total pipe length 15 or less 20 (Max.) 20 g/m...
  • Page 44: Airflow

    8. Airflow 8-1. AOBG09CMCA  Cooling 1,740 1,024 8-2. AOBG12CMCA  Cooling 1,700 1,001 - 40 - 8-1. AOBG09CMCA 8. Airflow...
  • Page 45: Operation Noise (Sound Pressure)

    9. Operation noise (sound pressure) 9-1. Noise level curve ¢ AOBG09CMCA  Cooling NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 NC-15 1,000 2,000 4,000 8,000 Octave band center frequency, Hz ¢ AOBG12CMCA  Cooling NC-65 NC-60 NC-55 NC-50 NC-45 NC-40...
  • Page 46: Sound Level Check Point

    9-2. Sound level check point Rear Microphone Microphone Airflow Side view Rear view NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above. - 42 - 9-2. Sound level check point 9. Operation noise (sound pressure)
  • Page 47: Electrical Characteristics

    10. Electrical characteristics Model name AOBG09CMCA AOBG12CMCA Voltage Power supply Frequency Maximum operating current* Starting current Circuit breaker current Power cable 1.0—1.5 Wiring Cross-sectional spec.* Connection area cable* Limited wiring length NOTES: • * : Maximum operating current is the total current of the indoor unit and the outdoor unit. •...
  • Page 48: Safety Devices

    11. Safety devices Model Type of Protection form protection AOBG09CMCA AOBG12CMCA 250 V, 20 A Circuit Current fuse (PCB*) protection 250 V, 5 A 103 ±18°C Activate Fan motor stop Fan motor Thermal protection protection 95 ±18°C Reset Fan motor restart 110°C Activate Compressor stop...
  • Page 49: Accessories

    12. Accessories 12-1. Models: AOBG09CMCA and AOBG12CMCA Part name Exterior Part name Exterior Installation manual - 45 - 12-1. Models: AOBG09CMCA and AOBG12CMCA 12. Accessories...

This manual is also suitable for:

Asbg12cmbaAobg09cmcaAobg12cmca

Table of Contents