Test procedure for functionality
As depicted 'ATTENTION' in above, the test for the functionality is important.
Please do the test following procedure.
(1) Please make each state of S1-SC and S2-SC depicted at Table.5.
(2) If there is any different state from Table.5, FR-D700-SC has some malfunction.
(3) If there is no different state from Table.5, check the systematic performance, such as, press the
Emergency switch, press the start/restart button at the failure detected (RUN-SE opened), and so on.
(4) Finally clear the error record of the FR-D700-SC (see the user manual how to clear the error record).

5. Safety parameters of FR-D700-SC

FR-D700-SC safety related I/O status obeys the following truth table.
Table.6 Safety parameters of FR-D700-SC
Parameter
PFD
AVG
PFH
D
PL
MTTF
D
DC
AVG
8
Value
-4
2.5x10
2.5x10
-9
d
500 years
60%