5.14

Oil scales

To enable or disable the scales operation, proceed as
follows:
1. Call up the Main Menu.
2. Select
.
3. Select
.
4. Select Settings.
5. Select Oil Load Cells.
6. Use the Up or Down arrow buttons to select the
scales to be modified: PAG Oil scale, POE Oil scale,
UV dye scale or Oil Drain scale.
7. Select
to enable or disable.
8. Select
to save.
5.15
Leak test vacuum time change
(except ACS 863-OE)
To change the leak test vacuum time, proceed as
follows:
1. Call up the Main Menu.
2. Select
.
3. Select
.
4. Select Settings.
5. Select Default Vaccum Leak Test Time.
6. Use the multi-touch interface on the numeric keypad
to change the value.
7. Select
to save.
5.16

Firmware update

To upgrade a firmware, proceed as follows:
1. Call up the Main Menu.
2. Select
.
3. Select
.
4. Select Settings.
5. Select Firmware Update.
6. Use the Up or Down arrow buttons to select the
desired mode.
7. Select
to proceed.
8. Follow the instructions on the display.
i
To upgrade the firmware with USB key, insert the
key into the USB port on the control panel and
display the station; while the firmware upgrade via
WiFi is necessary before connecting the station to a
WiFi network (see chapter 5.17).
Robert Bosch GmbH
Initial settings | ACS 763/863 | 59
5.17

Wifi configuration

1
Fig. 16:
USB port location
1 USB ports
1. Carefully insert the WiFi Dongle into the USB
connector of the station.
2. Turn on the station and pair the Dongle with the
Router on.
3. Call up the Main Menu.
4. Select
.
5. Select
.
6. Select Settings.
7. Select WiFi Configuration.
8. Select Search WiFi Networks and wait a few
seconds to display the available networks.
9. Select the network associated with the router with
the Up or Down arrow buttons and confirm with
10. Enter the router WiFi password, confirm with
and wait for the connection to be established.
i
Make use of Manual Connect function whenever the
WiFi network is not automatically detected through
the Search WiFi Networks function. Manually
enter the WiFi network name and password paying
attention to upper and lower cases and then confirm
with
.
11. The station informs the operator with a message
that the connection has been successfully
completed and the status bar will appear
12. Select
to exit.
"
The configuration to WiFi network is completed.
i
The efficiency and quality of wireless
communication may be affected by the presence
of radio disturbances. The protocol provides for
handling errors, but can cause communication
problems that sometimes require new attempts to
connect. If there are critical features that may affect
normal operation, the source of electromagnetic
environmental noise must be sought, reducing its
intensity.