TC(℃)
Fgh_t1-2
Fgh_t2-2
Fgh_t3-2
Fgh_t4—2
Fgh_t5—2
Normal
N:Decreasing at the speed of 1HZ/1 second
P:Decreasing at the speed of 1Hz/10 seconds
Q:Continue to keep the last-time instruction cycle
R:Increasing at the speed of 1Hz/10seconds
Remarks: the outdoor unit
7.1.5.3 The control of preventing the over current of the compressor:
●During the starting process of the compressor, if the current of the compressor is greater than 17A
for 3 seconds, stop the compressor and alarm, after 3 minutes, start it again, if such state appears 3
times in 20 minutes, stop the compressor and alarm, and confirm the malfunction. Then continue to
run it only after the power is off.
●During the starting process of the compressor, if the AC current is greater than 15A, the frequency
of the compressor decreases at the speed of 1HZ/second.
●During the starting process of the compressor, if the AC current is greater than 14A, the frequency
of the compressor decreases at the speed of 0.1HZ/second.
●During the starting process of the compressor, if the AC current is greater than 13A, the frequency
of the compressor increases at the prohibited speed.
●During the starting process of the compressor, if the AC current is greater than 12A the frequency of
the compressor increase
7.1.5.4 The protection function of AC current:
During the starting process of the compressor, if the
stop the compressor and alarm, after 3 minutes, start it again, if such state appears 3 times in 20
minutes, stop the compressor and alarm, and confirm the malfunction. Then continue to run it only
after the the power is off.
During the starting process of the compressor, if the AC current is greater than 15A, the frequency of
the compressor decreases at the speed of 1HZ/second.
During the starting process of the compressor, if the AC current is greater than 14A, the frequency of
the compressor decreases at the speed of 0.1HZ/second.
During the starting process of the compressor, if the AC current is greater than 13A, the frequency of
the compressor increases at the prohibited speed.
During the starting process of the compressor, if the AC current is greater than 12A, the frequency of
the compressor increases at the speed of no faster than 0.1HZ/second.
Remarks: when the outdoor temperature is high, there's compensation for AC current protection.
The compressor stops
N Decreasing the frequency rapidly
P Decreasing the frequency slowly
Q Prohibiting increasing the frequency
R Increasing slowly
s at the speed of no faster than 0.1HZ/second.
AC current is greater than 17.5Afor 3 seconds,
18
Domestic air conditioner
Functions and control
Fgh_t1 63℃
Fgh_t2 59℃
Fgh_t3 56℃
Fgh_t4 53℃
Fgh_t5 40℃