Hitachi CSNET MANAGER XT Installation And Operation Manual page 57

Table of Contents

Advertisement

Address
Name
(note 1)
17
TGAS
18
TLIQUID
19
ERROR_CODE
20
STOP_CAUSE
21
22
OPER_CONDITION
23
DEFROS
24
AMBIENT_TEM
25
RCS_TEMP
26
TIMER_DISABLED
27
OPTIONS
28
POWER
29
COMP_QTY
30
COMP_FREQ
31
REM_TEMP
N O T E
1
2 These numbers refer to signed 16-bit value using 2-complement format for negative values.
3
4
5 Indoor unit consumption percentage in relation to all the installation power consumption
51
PMML0409A rev.1 - 10/2016
Description
Gas pipe temperature (Note 2)
Liquid pipe temperature (Note 2)
Alarm code
Compressor stop cause
Indoor unit expansion valve opening
Unit operation condition
0: OFF
1: Thermo OFF
2: Thermo ON
3: Alarm
Defrost
Ambient temperature (Note 2)
Remote control switch temperature
(Only when available in unit) (Note 2)
Timer disabled
0: Enabled
1: Disabled
Options setting (Note 6)
Calculated power consumption (Note 5)
Running compressor quantity (Note 3)
Inverter compressor frequency
Remote sensor temperature
(Only when accessory is installed) (Note 2)
R/W
R
R
R
R
R
R
R
R
R
R/W
R
R
R
R
R