Unit memory
number
Name
(Hex)
UM 00110
UM 00120
Lower limit of upper and
lower output clipping
UM 00130
UM 00140
UM 00111
UM 00121
Analog output in PROG.
mode
UM 00131
UM 00141
(Note 1)
The unit memory numbers in the above table are listed for CH0, CH1, CH2, and CH3 in numerical
order.
WUME-FP7AOH-03
Default
Setting range and description
Set the lower limit to turn ON the upper limit relay for
the use of the function of clipping upper and lower
output.
K0
Setting range: -32,500 to +32,500 (Specified with a
signed integer)
Set a digital value corresponding to the analog
output when a desired value is set for the analog
output in PROG. mode.
K0
Setting range: -31,250 to +31,250 (Specified with a
signed integer)