06 Electrical Connection

6 Electrical Connection

6.1 Circuit Diagram

• N and PE wiring via ON-GRID and BACK-UP ports of the inverter are different based on the
regulation requirements of different regions. Refer to the specific requirements of local
regulations.
• There are built-in relays inside of the inverter's ON-GRID and BACK-UP AC ports. When the
inverter is in the off-grid mode, the built-in ON-GRID relay is open; while when the inverter
is in grid-tied mode, it is closed.
• When the inverter is powered on, the BACK-UP AC port is charged. Power off the inverter
first if maintenance is required for the loads connected with BACK-UP ports. Otherwise, it
may cause electric shock.
• Only GEH series inverters support PV
N and PE cables are connected together in the Main Panel for wiring.
Below wirings are applicable to areas in Australia, New Zealand, South Africa, and etc.
Inverter
BAT
Battery
BMS
PV
PV
String
L
N
BACK-UP
Do not wire in this position
PE
or
if N and PE cables are
connected together.
Meter
L
ON-GRID
N
PE
PE
NOTICE
string connection.
NOTICE
Main Panel
Smart Meter
RCD
N-BAR
L
N
PE
Normal Load
24
User Manual V1.1-2023-06-20
RCD
CT
E-N Link
E-BAR
L
N
BACK-UP
Load
PE
L
Utility
N
Grid
PE