Table 6. Settings (continued)
Description
Unsynchronized Transfers
External Battery Module (EBM)
Charger
Battery Charge % to Restart
Battery Low Alarm
Automatic Battery Tests
Reset Peak Consumption Watts
Reset Cumulative Consumption
kWh
Available Settings
[Enabled] [Disabled]
If Enabled, unsynchronized transfers to the Bypass
are allowed.
If Disabled, unsynchronized transfers to the Bypass
are not allowed.
The Qualify Bypass setting may overrule the
NOTE:
Unsynchronized Transfers setting.
[0] [1]
See "Configuring the UPS for an EBM" on page 52.
[Enabled] [Disabled]
If Enabled, batteries charge normally.
If Disabled, the battery charger is off.
[0 %] [10%] [20%] [30%]...[100%]
When enabled, automatic restart is made when the
battery charge state reaches the selected level. If set
to 0, the feature is disabled.
[Immediate] [2 min] [3 min] [5 min]
If you select a value, the battery low alarm triggers
when the set amount of backup time
(approximately) remains in the batteries.
If Immediate, the battery low alarm activates at the
same time as the "UPS on Battery" notice.
[Enabled] [Disabled]
See "Running Automatic Battery Tests" on page 53.
[No] [Yes]
If No, no action.
If Yes, the Peak Consumption Watts value is
cleared and the date and time stamp for this
statistic is set to the current date and time.
[No] [Yes]
If No, no action.
If Yes, the Cumulative Consumption kWh value is
cleared and the date and time stamp for this
statistic is set to the current date and time.
Default Setting
Enabled
0
Enabled
0 %
3 min
Enabled
No
No
|
45