Motorola V186 - Cell Phone - GSM System Planner Manual page 166

Remote terminal unit (rtu)
Hide thumbs Also See for V186 - Cell Phone - GSM:
Table of Contents

Advertisement

120/230V 12DO Relay Modules
Total Number of Outputs
Output Arrangement
Contact Power Ratings
Minimum Contact Load
Current
Maximum Switching Current
Relay Back Indication
DO Frequency
Diagnostic LEDs
User Connection
Cable and TB Holder
Fail State
All Relays Disable/Enable
Module Replacement
Output Isolation
Insulation
Operating Voltage
Power Consumption
Dimensions
Weight
Specifications subject to change without notice.
12 EE relay outputs
12 ML relay outputs
12 x 1 Form A
3A @ 250 V AC, 3A @ 30 V DC, or 0.20A @ 125 V DC (resistive load)
10.0 mA @+5.00 V DC
3.00 A
Contact position - hardware back indication
Max. 10 Hz (resistive load)
LED per each output status, module error LED
3 Terminal Blocks (5.00mm pitch), Maximum 14 AWG
30 Wire Cable with Terminal Block Holder connector, 20 AWG
Configurable relay state on CPU fail: On, Off or 'last value'
Selectable per module, controlled from the power supply
Hot swap replacement – module extraction/insertion under voltage
Between output and module logic 2.5 kV per IEC60255-5
Insulation resistance 100 MΩ @ 500 V DC per IEC60255-5,
Insulation impulse 5 kV per IEC60255-5
10.8-16 V DC and 3.3 V DC ±10% (from the motherboard connector)
Refer to Appendix C: ACE3600 Maximum Power Ratings.
37 mm W x 225 mm H x 180 mm D (1.5" W x 8.7" H x 7.1" D)
approx. 0.423 kg (0.90 lbs)
162
Appendix A – ACE3600 Specifications