Mixed I/O Module Specifications - Motorola V186 - Cell Phone - GSM System Planner Manual

Remote terminal unit (rtu)
Hide thumbs Also See for V186 - Cell Phone - GSM:
Table of Contents

Advertisement

Mixed I/O Module Specifications

Total Number of Inputs / Outputs 16 Digital Inputs + 4 EE Relay Outputs + 4 Analog Inputs
I/O Arrangement
DI Counter Inputs
DI Frequency
DI Fast Counter Frequency
DI Max. DC Voltage
DI "ON" DC Voltage Range
DI "OFF" DC Voltage Range
DI Current
Fast Capture Resolution
Event Time Tagging Resolution
DI Filtering
DI Counter Filtering
DO Contact Voltage Ratings
DO Contact Power Ratings
DO Relay Back Indication
DO Fail State
AI Resolution
AI Accuracy
AI Sampling Time
AI Smoothing
AI max. Potential between AIs
AI Impedance
AI Crosstalk Rejection
AI Temperature Stability
Appendix A – ACE3600 Specifications
( ±20 mA) (Option V245)
16 Digital Inputs + 4 ML Relay Outputs + 4 Analog Inputs
( ±20 mA) (Option V453)
1 group of 16 DIs with shared common
4 relay outputs - Form C
4 isolated analog inputs
The first 12 inputs can be configured as fast counters.
0 - 1 KHz
0 - 5 KHz, minimum pulse width 100 µS
Max. 40 V DC
+11 to +30 V DC, -30 to -11 V DC
-5 to +5 V DC
6-10 mA
1 mS (Interrupt upon change of state)
1 mS (Interrupt upon change of state)
0 to 50.8 mS (DC, programmable in 0.2 mSec steps)
0 to 12.75 mS (programmable in 0.05 mSec steps for inputs
configured as high speed counters)
Max. 60 V DC or 30 V AC RMS (42.4 V peak).
2A @ 30 V DC, 0.6A @ 60V DC or 0.6A @ 30V AC
(resistive load)
Contact position - hardware back indication
Configurable relay state on CPU fail: On, Off or 'last value'
16 Bit (including sign)
±0.1% full scale @ -40ºC to +70ºC
10 mSec @ 50 Hz filtering
8.33 mSec @ 60 Hz filtering
Selectable input averaging: 1, 2, 4, 8, 16, 30, 60 or 128
samples (x10 mS)
75 V DC, 60 V AC (RMS)
Rin < 250 Ω
Better than 80 dB between any pair of inputs
25 PPM/ºC
165