Hitachi L300P Series Instruction Manual page 119

Three-phase input 200v class; three-phase input 400v class;
Hide thumbs Also See for L300P Series:
Table of Contents

Advertisement

Option
Terminal
Code
Symbol
28
DWN
Remote Control
DOWN Function
(motorized speed pot.)
29
UDC
Remote Control Data
Clearing
31
OPE
Operator Control
32
SF1
Multispeed bit 1
33
SF2
Multispeed bit 2
34
SF3
Multispeed bit 3
35
SF4
Multispeed bit 4
36
SF5
Multispeed bit 5
37
SF6
Multispeed bit 6
38
SF7
Multispeed bit 7
39
OLR
Overload restriction
49
ROK
Run Enable for FW/RV
*1
(–xFU2 and –xFE2
models only)
no
Not selected
Note 1: To ensure safe inverter operation in networked applications, you cannot change an
Input Function Summary Table
Function Name
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
intelligent terminal assignment to/from [ROK] (option code 49) via the network.
However, you can still read an [ROK] input assignment over the network.
Description
Decelerates (decreases output frequency) motor from
current frequency
No change to output frequency
Clears the UP/DWN frequency memory by forcing it
to equal the set frequency parameter F001. Setting
C101 must be set=00 to enable this function to work.
UP/DWN frequency memory is not changed
Forces the source of the output frequency setting
(A001) and the source of the RUN command (A002)
to be from the digital operator
Source of output frequency set by (A001) and source
of run command set by (A002) is used
Logical 1
Logical 0
Logical 1
Logical 0
Logical 1
Logical 0
Logical 1
Logical 0
Logical 1
Logical 0
Logical 1
Logical 0
Logical 1
Logical 0
Selects current overload parameter set 2
(B024, B025, B026)
Selects current overload parameter set 1
(B021, B022, B023)
[FW] and [RV] inputs and operator Run key press
operate normally
[FW] and [RV] inputs and operator Run key press are
ignored; inverter output remains OFF
(input ignored)
(input ignored)
3–47
L300P Inverter