Combustion Air And Ventilation For Appliances In Unconfined Spaces; Combustion Air And Ventilation For Appliances In Confined Spaces - Kenmore 153.334590 Owner's Manual

Gas water heater
Table of Contents

Advertisement

Installation
Instructions
(cont'd)
Combustion Air and Ventilation
for Appliances Located in
Unconfined Spaces
Unconfined
Space is a space whose volume is not less than 50
cubic feet per 1,000 Btu per hour of the aggregate input rating
of all appliances installed in that space. Rooms communicating
directly with the space in which the appliances are installed,
through openings not furnished with doors, are considered a
part of the unconfined space.
In unconfined spaces in buildings, infiltration may be adequate
to provide air for combustion,
ventilation and dilution of"flue
gases. However, in buildings of tight construction
(for example,
weather stripping, heavily insulated, caulked, vapor barrier, etc.),
additional
air may need to be provided
using the methods
described in Combustion
Air and Ventilation
for Appliances
Located in Confined Spaces, b.
Combustion Air and Ventilation
for Appliances Located in
Confined Spaces
,
Contined
Space is a space whose volume is less than 50 cubic
feet per 1,000 Btu per hour of the aggregate input rating of all
appliances installed in that space.
a_ ALL AIR FROM INSIDE BUILDINGS:
(See Page 9 Figure 1, and Figure 2 below)
The confined space shall be provided with two permanent
openings communicating
directly with an additional room(s)
of sufficient
volume so that the combined
volume of all
spaces meets the criteria for an unconfined
space. The total
input of all gas utilization
equipment
installed in the com-
bined space shall be considered in making this determination.
Each opening shall have a minimum
flee area of one square
inch per 1,000 BTU per hour of the total input rating of all
gas utilization equipment in the confined space, but not less
th,an 100 square inches. One opening shall commence within
12 of the top and one commencing
within 12 of the bot-
tom of the enclosure.
1. When directly communicating with the outdoors, each open-
ing shall have a minimum free area of I square inch per 4,000
BTU per hour of total input rating of all equipment in the
enclosure. (See Figure 3.)
2. When communicating with the outdoors through vertical
ducts, each opening shall have a minimum free area of 1
square inch per 4,000 BTU per hour of total input rating of
all equipment in the enclosure. (See Figure 4.)
Figure 4 ]
3. When communicating
with the outdoors through horizontal
ducts, each opening shall have a minimum
free area of 1
_[_uareinch per 2,000 BTU per hour of total input rating of
equipment in the enclosure. (See Figure 5.)
Figure 2 ]
b, ALL AIR FROM OUTDOORS:
(see Figures 3-5)
The confined space shall be provided with two permanent
openings, one commencing within 12" of the :op and one
commencing within 12" from the bottom of t!_eenclosure.
The openings shall communicate directly,or b, ducts, with
the outdoors or spaces (crawl or attic) that free communi-
care with the outdoors.
Figure 3 I
Figure 5 ]
10
4. When ducts are used, they shall be of the same cross-sectional
area as the flee area of the openings to which they connect.
The minimum short side dimension of rectangular air ducts
shall not be less than 3". (See Figure 5.)
5.
Louvers and Grilles: In calculating
free area, consideration
shall be given to the blocking effect of louvers, grilles or
screens protecting openings. Screens used shall not be smaller
than ¼-mesh.
If the free area through a design of louver or
grille is known, it should be used in calculating the size open-
ing required to provide the free area specified. If the design
and free area is not known, it may be assumed that wood lou-
vers will be 20-25 percent free area and metal louvers and
grilles will have 60-75 percent free area. Louvers and grilles
shall be f'Lxedin the open position or interlocked
with the
equ!pment
so that they are opened automatically during
equipment
operation,
6. Special Conditions Created by Mechanical Exhausting or
Fireplaces: Operation of exhaust fans, ventilation systems,
clothes dryers or fireplaces may create conditions requiring
special attention to avoid unsatisfactoryoperationof installed
gasutilization equipment.

Advertisement

Table of Contents
loading

Table of Contents