Combustion Air And Ventilation For Appliances Located In Unconfined Spaces; Combustion Air And Ventilation For Appliances Located In Confined Spaces - Kenmore 153.338400 Owner's Manual

40/50/75 gal. / high altitude
Table of Contents

Advertisement

0
_'ombustion Air and Ventilation
for Appliances Located in
Unconfined
Spaces
Unconfined Space is a space whose volume is not less than 50
cubic feet per 1,000 Btu per hour of the aggregate input rating
of all appliances installed in that space. Rooms communicating
directly with the space in which the appliances are installed,
through openings not furnished with doors, are considered a
part of the unconfined space
fn unconfined spaces in buildings, infiltration
may be adequate
to provide air for combustion,
ventilation
and dilution
of flue
gases. However, in buildings of tight construction
(for example,
weather
stripping,
heavily insulated,
caulked, vapor barrier,
etc.), additional air may need to be provided using the methods
described
in Combustion
Air and Ventilation
for Appliances
Located in Confined Spaces.
Combustion Air and Ventilation
for Appliances Located in
Confined Spaces
Confined Space is a space whose volume is less than 50 cubic
feet per 1,000 Btu per hour of the aggregate input rating of all
appliances installed in that space.
a, ALL AIR FROM INSIDE BUILDINGS:
(See Page 8 Figure 1, and Figure 2 below)
The confined space shall be provided with two permanent
openings communicating directly with an additional
room(s)
of sufficient
volume
so that the combined volume
of all
spaces meets the criteria for an unconfined space. The total
input of all gas utilization equipment installed in the com-
bined space shall be considered in making this determina-
tion. Each opening shall have a minimum
free area of one
square inch per 1,000 BTU per hour of the total input rating
of all gas utilization
equipment
in the confined space, but
not less than 100 square inches. One opening shal] com-
mence within
12 inches of the top and one commencing
within 12 inches of the bottom of the enclosure.
h-n
[
]
b. ALL AIR FROM OUTDOORS:
(see Figures 3-5)
The confined
space shall be provided
with two perma-
nent openings, one commencing
within
12 inches of the
top and one commencing
within
12 inches from the bot-
tom of the enclosure.
The openings
shall communicate
directly, or by ducts, with the outdoors or spaces (crawl or
attic) that freely communicate
with the outdoors.
1. When directly
communicating
with the outdoors,
each
opening shall have a minimum
free area of 1 square inch
per 4,000 BTU per hour of total input rating of all equip-
ment in the enclosure. (See Figure 3.)
2. When communicating
with the outdoors through vertical
ducts, each opening sha[t have a minimum
free area of 1
square inch per 4,000 BTU per hour of total input rating
of all equipment
in the enclosure. (See Figure 4.)
Q_IIdNEY I:>FtGAS VENT
Figure 4 ]
3. When communicating with the outdoors through horizon-
tal ducts, each opening sh_.ll have a minimum free area of
1 square inch per 2,000 BTU per hour of total input rating
of all equipment in the enclosure. (SeeFigure 5.)
Figure 5 I
4. When ducts are used, they shall be of the same cross-sec-
tional area as the free area of the openings to which they
connect. The minimum
short side dimension of rectangular
air ducts shall not be less than 3 inches. (See Figure 5.)
5. Louvers and Grilles: In calculating free area, consideration
shall be given to the blocking
effect of louvers, grilles or
screens protecting
openings.
Screens used shall not be
smaller than '/4 inch mesh. If the free area through a design
of louver or grille is known, it should be used in calculat-
ing the size opening required to provide the free area spec-
ified. If the design and free area is not known,
it may be
assumed that wood louvers will be 20-25 percent free area
and metal louvers and griIIes will have 60-75 percent free
area. Louvers and grilles shall be fixed in the open position
or interlocked with the equipment so that they are opened
automatically
during equipment operation.
6. Special Conditions
Created by Mechanical
Exhausting or
Fireplaces: Operation
of exhaust fans, ventilation
systems,
clothes dryers or firepJaces may create conditions
requiring
special
attention
to avoid
unsatisfactory
operation
of
installed gas uti]ization equipment.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents