Http Server Functions/ Web Pages
Please note that the string at DT600 needs to be initialized by the PLC program before data can
be stored there. Also see second note in "Notes on Strings", Defining Input Fields for PLC Data
on HTML Pages (see "Defining Input Fields for PLC Data on HTML Pages" on page 87).

7.1.14 Automatic Page Reload upon Submitting PLC Data

If the html file "s_m_done.htm" is uploaded to the FP Web-Server
the html code of this file will be reloaded to the browser after submitting PLC data. The following
default window will be replaced by displaying the file "s_m_done.htm".
Example 1: Automatic refresh of an html page after sending PLC data
Enter the following lines in the file "s_m_done.htm":
<html><head><title>DONE</title></head><body>
<script language="JavaScript">
opener.location.reload(true);
window.close();
</script></body></html>
Comments:
This script also automatically closes the default window OK or DONE
Find a copy of this file in \\Example4\http in your installation directory
Using this file you can execute Java Script applications after sending PLC data
The file "s_m_done.htm" may not contain PLC data fields, e.g. {DT100_6_d}
the IEC Configurator after you have modified the file "s_m_done.htm". (When
Restart
modifying other htm files the unit does not have to be restarted.)
Example 2: Automatic refresh of an html page after sending PLC data but without
closing the OK window automatically
Using this script you have to click [OK] to close the OK window
<html><head><title>DONE</title></head><body>
<p align="center"><font face="Arial"><strong><big>FP
Web-Server</big><br>
</strong><small>Data values transfered to PLC.</small></font></p>
<form><div align="center"><center><p>
<input type="button" value="OK" + " onClick="self.close()"></p>
</center></div></form>