When Connected To Modbus; When Connected To A Plc Made By Toshiba Machine Co., Ltd - Panasonic GT01 User Manual

Gt series programmable display
Hide thumbs Also See for GT01:
Table of Contents

Advertisement

5.3.6 When Connected to Modbus

For GT01, GT11 and GT21
Code No.
Time up error
ERFF
There is no response
from the PLC.
Response error
There is an abnormal
ERFE
response returned
from the external
device.
For GT02, GT02L, GT05, GT12, GT32 and GT32-E
Code No.
Time up error
**0001
There is no response
from the PLC.
Response error
There is an abnormal
**ERFE
response returned
from the external
device.

5.3.7 When Connected to a PLC Made by Toshiba Machine Co., Ltd.

For GT02, GT02L, GT05, GT12, GT32 and GT32-E
Code No.
ERFFFE
Parameter errror
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Content
1) PLC connection cable is disconnected. Check the wiring of
the connection cable and check for disconnection.
2) It is a temporary error caused by noise, etc. Turn on the
power supplies for PLC or GT again.
Check the data to be returned from the external device.
Content
1) PLC connection cable is disconnected. Check the wiring of
the connection cable and check for disconnection.
2) It is a temporary error caused by noise, etc. Turn on the
power supplies for PLC or GT again.
Check the data to be returned from the external device.
Content
The specified parameter does not exist, or it cannot be used.
Cause and solution
Cause and solution
Cause and solution