Input And Output Terminal Specifications - GE SERIES B 480 User Manual

480 volts, 60hz
Table of Contents

Advertisement

g
INSTALLATION INSTRUCTIONS - continued
Filter
Rating(Amps)
6
8
11
14
21
27
34
44
52
66
83
103
128
165
208
240
320
403
482
636
786
GEH-7252

Input and Output Terminal Specifications

Input Terminals
Wire Range
Terminal Torque
(AWG)
22 -14
22 - 14
22 - 14
22 - 5
22 - 5
22 - 5
22 - 5
18 – 4
18 – 4
6-4
2-0
6-4
2-0
6-4
2-0
6-4
2-0
2 – 0000
2 – 0000
2-0000
00
000-0000
250-350 MCM
500 MCM
00
000-0000
250-350 MCM
500 MCM
NA
NA
30
GE Capacitor & Power Quality Products
Table 8
Wire Range
(in-lbs)
(AWG)
4.5
22 – 14
4.5
22 – 14
4.5
22 – 5
16
22 – 5
16
22 – 5
16
18 – 4
16
18 – 4
20
18 – 4
6-4
20
2-0
45
6-4
50
2-0
45
6-4
50
2-0
45
6-4
50
2-0
45
2-0000
50
150
2 – 0000
150
2 – 0000
00
000-0000
150
250-350 MCM
500 MCM
180
00
250
000-0000
325
250-350 MCM
375
500 MCM
180
00
250
000-0000
325
250-350 MCM
375
500 MCM
NA
NA
NA
NA
May 2003
Output Terminals
Terminal Torque
(in-lbs)
4.5
4.5
16
16
16
20
20
20
45
50
45
50
45
50
45
50
150
150
150
180
250
325
375
180
250
325
375
180
250
325
375
NA
NA

Advertisement