Toshiba AD268 User Manual page 21

Programmable controller prosec t2-series analog i/o modules
Table of Contents

Advertisement

PART 1 AD268
5V range:
Upper limit
Full scale (positive)
Full scale (negative)
Lower limit
-10.2V
HC180
-16000
Lower limit
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Input voltage
+5.1196 V
:
+5 V
:
+0.3125 mV
0
0 V
-0.3125 mV
:
-5 V
:
-5.12 V
Digital value
+5V
H3FFF
16383
0
-5.12V
+5.1196V
HC000
-16384
-5V
5. I/O Allocation and Programming
A/D conversion data
Hexadecimal
H3FFF
:
H3E80
:
H0001
H0000
HFFFF
:
HC180
:
HC000
Upper limit
H3E80
16000
Analog input
+10.2V
Resolution
Integer
16383
:
16000
:
1
0
0.3125 mV / bit
-1
:
-16000
:
-16384
D = 3200
A
D: Digital data
A: Analog signal (V)
User's Manual
19