Specifications - GE T5000 Series Specifications

T5000 series co2/temperature transmitter

Advertisement

T5000 Series

Specifications

Product
Sampling Method
Non-dispersive infrared (NDIR), gold plated optics, (with
Telaire's patented ABC Logic self calibration algorithm).
Diffusion sampling.
Measurement Range
0 to 2,000 ppm factory calibrated.
Accuracy
± 75 ppm @ 72°F (22°C) when compared with a factory
reference or 10% of reading, whichever is greater*
Temperature Dependence
0.2% FS per °F (°C)
Stability
<2% of FS over life of sensor (15 years typical)
Non-Linearity
<1% of FS
Pressure Dependence
0.13% of reading per mm Hg
Calibration Interval
Not required*
Response Time
3 to 5 minutes for 90% step change.
Warm up Time
• <2 minutes (operational)
• 10 minutes (maximum accuracy)
Operating Conditions
• 32°F to 122°F (0°C to 50°C)
• 0 to 95% RH, non condensing
Storage Conditions
• -4°F to 158°F (-20°C to 70°C)
• 0 to 95% RH, non condensing
Temperature
NTC 20k thermistor
Output
• Analog: 0 to 10V or 0 to 5V
Connections
Screw terminals for 18 to 28 AWG
Power Supply Requirements
18 to 30 VAC RMS, 50/60Hz or 18 to 42 VDC, polarity
protected
Power Consumption
1.75 VA average, 2.75 VA peak
Agency/Certifications
FCC Part 15 Class B, CE, RoHS, WEEE
Warranty Term
18 months
* Note: Automatic Background Calibration, or ABC Logic,
is a patented self-calibration technique designed to be
utilized in applications where concentrations will drop
to outside ambient conditions (approximately 400 ppm)
at least four times in a 14-day period, typically during
unoccupied periods.
Full accuracy is achieved after two weeks of operation.