Specifications

General
Terminal ratings
Approvals
Environmental
ratings
4/12
Siemens Building Technologies
Supply voltage
100 Vac –15 % ... 110 Vac +10 % 50/60 Hz ±6 %
220 Vac –15 % ... 240 Vac +10 % 50/60 Hz ±6 %
Internal fuse
External fuse
Weight – LFL
Weight – Wiring base
Power consumption
Mounting orientation
Terminal 1
Line
Terminal 2
Neutral
Terminal 3
Alarm
Terminals 4 to 5
Limit string
Terminals 6 and 7
Combustion Air
Terminals 8, 9, 10, 11 Damper actuator
Terminals 12, 13, 14
Air flow interlock
Terminal 16
Ignition transformer
Terminal 17
Pilot fuel valve
Terminal 18
Main fuel valve
Terminal 19
Main fuel valve
Terminal 20
Damper actuator
UL
File:
MH26134
CSA
Certificate: 1370843
FM
File:
J.I. 3003560
CE
File: CE-0085AP0001
FCC
Compliant
Vibration
Operation temperature range
Storage temperature range
of water are not permitted!
6.3 A (slow)
Maximum 10 A (slow)
2.2 lb
0.25 lb
3.5 VA
No restrictions
Maximum 5 A total load
N/A
1 A pilot duty
N/A
Motor 4 FLA, 24 LRA or 1.6 A pilot duty
Blower
N/A
N/A
4 A
Motor 4 FLA, 24 LRA or 1.6 A pilot duty
Motor 4 FLA, 24 LRA or 1.6 A pilot duty
Motor 4 FLA, 24 LRA or 1.6 A pilot duty
N/A
110V
Standard: UL372
Standard: CAN/CSA-C22.2 No 199-M89
Standard: FM7610
110V & 220V
Standard: DIN EN 298
Part 15 Class B - Emissions
0.5G Environment
-5...+140 °F
-58...+140 °F
Condensation, formation of ice and ingress
< 95 % relative humidity
< 95 % relative humidity
HVAC Products
11.15.2004