LRM2070, LRM2080, LRM2090 Datasheet
OccuSwitch DALI sensor/controller
Electrical installation
The OccuSwitch DALI can be installed with either conventional wiring
or Wieland connectors. For the second option, the Wieland cable
(LCC2070 or LCC2080) is required. The OccuSwitch DALI comes
with a detachable mains connector for easy installation. This connector
is removed if the Wieland cable is used. The mains connection is
protected by a retractable cover and secured with two tie wraps.
2
4
LCC2070 or LCC2080
The DALI signal from a driver or luminaire, although low voltage and
isolated from mains, cannot be treated as a safe signal (SELV). All wiring
and isolation materials used must be similar to mains wiring (FELV).
The same applies to the network connection of the LRM2080 and
LRM2090.
1
3
5
LRM2070
–
X
+
–
DA
+
na
N
L
L
N
LRM2080
LRM2090