E6: Cycle Skip, Accel.

E7: Analog Out Error

E30: Channel Disabled

E31: Invalid Calibration

Error Codes and Diagnostics
Problem: The acceleration exceeds the limits programmed in the
Error Limits option of the User Program.
Cause:
This condition is usually caused by poor flow conditions
or improper transducer alignment.
Action:
Refer to the sections on Fluid and Pipe Problems (page
6-6) and on Transducer Problems (page 6-8) to correct
any problems.
Problem: The current setting is outside the programmed limits.
Cause:
The calculated output value exceeds the programmed
limits.
Action:
Verify that the 4-20 loop configuration base and span
settings are correct for your process.
Problem: The channel is not available.
Cause:
The channel has been turned off.
Action:
Enter the PROGRAM menu and enable the channel (see
page 2-4).
Problem: The calibration is invalid.
Cause:
Improper calibration for the application has been entered.
Action:
Consult GE Panametrics.