Test Instructions For Fap-Dotc420 / Fap-Dot420 / Fap-Otc 420 / Fap-Ot 420; Warranty; Repair - Bosch FAP-DO420 Operation Manual

Automatic fire detectors lsn improved
Hide thumbs Also See for FAP-DO420:
Table of Contents

Advertisement

Automatic Fire Detectors LSN
improved
8.3.2
Test Instructions for FAP‑DOTC420 / FAP‑DOT420 / FAP‑OTC 420 /
FAP‑OT 420
Sequential walktest
Select walktest type "Sequential walktest" on the FPA-5000/FPA-1200 panel controller in the
walktest menu.
Notice!
The test head must remain over the detector until the detector has been triggered. The time
i
taken to distribute the test aerosol in the test head and therefore the trigger time of the sen-
sor can be up to 20 seconds.
Simultaneous walktest
Select walktest type "Simultaneous Walktest" on the FPA-5000/FPA-1200 panel controller in
the walktest menu.
Multisensor detectors can be tested simultaneously with the FME-TESTIFIRE multi-stimulus
test tool. Observe the notes in the detector testing device and fire panel operating
instructions.
Notice!
i
An alarm message is only displayed on the panel if all sensors are triggered during the simul-
taneous walktest. If this does not happen, one of the sensors is faulty.
Testing outside the Revision Mode
Detectors of the FAP-OTC 420 und FAP-DOTC 420 types can be triggered outisde of the
revision mode only by the following stimuli:
8.4

Warranty

Defective detectors are exchanged free of charge in the case of a claim under the warranty.
8.5

Repair

In the event of a defect, the entire detector is exchanged.
Bosch Sicherheitssysteme GmbH
FAP‑0 420 and FAP‑DO420 Trigger the detector with a testing aerosol. Depending on the
sensitivity settings, it can take up top 1 minute till the detector goes off. It is
recommended to apply the aerosol in spurts (for example one short spurt of 1 second, 30
seconds of waiting, another short spurt).
All other detector variants:
Trigger the T-piece.
The same test device is used to test the CO sensor in the FAP‑DOTC420 / FAP‑OTC 420.
You only need to exchange the Solo A3-001 testing gas bottle with the CO testing gas
bottle. The testing gas must be applied for 1/2 to 1 second for the CO test.
The thermal sensor of the FAP‑DOTC420 / FAP‑DOT420 / FAP‑OTC 420 / FAP‑OT 420 is
tested with the test device for heat detectors.
Rise of temperature according to the sensitivity settings A2R, A2S, BR, and BS as defined
by EN 54-5
Simultaneous creation of artificial smoke and CO (by a suitable multi-stimulus test tool,
like FME-TESTIFIRE)
Simultaneous creation of artificial smoke and rise of temperature (by a suitable multi-
stimulus test tool, like FME-TESTIFIRE)
Operation Guide
Maintenance and Service | en
12/2012 | 8.1 | F.01U.003.448