Conventional Fire Panel
1 2 3 4 5 6 7 8
Level 2 Code
Confirm: ____
You then have to confirm the new code by entering it again.
The procedure for changing the code for operating level 3 is
exactly the same.
Notice!
If you have forgotten your code, contact your Bosch partner.
4.1.8

Test Log

You can decide whether or not the fire panel creates a Test
History.
1
8
1
4.2

Configuring Delays

In the Delay Config menu, you can program different delay
times for different zone programs, outputs and fault types.
2
Bosch Sicherheitssysteme GmbH
Press zone key 1. This takes you to the System
Config menu.
Press zone key 8.
This takes you to the Test History submenu.
Use zone keys 1 or 2.
2
1=Log Enabled (default setting)
...
2 Log Disabled
Press zone key 2. This takes you to the Delay Config
menu.
System Configuration | en
2014.06 | 7.0 | F.01U.172.980
39