Conventional Fire Panel
No delay (No Delay)
A zone programmed as No Delay triggers an alarm immediately.
If you are using manual call points, they must be set as No
Delay.
Notice!
Only use manual call points in zones which are programmed as
No Delay.
Int Alarm StorIntermediate alarm storage
A zone triggers an alarm. This is evaluated by the fire panel as a
pre-alarm and is not displayed. The zone is reset automatically.
If it triggers an alarm again, the panel switches immediately to
alarm. If a second alarm is not triggered, the fire panel reverts to
its normal state after 10 minutes.
Alarm verification (Alarm Verific)
Notice!
Note that the delay is only effective in day mode. In night mode,
the alarm is triggered immediately.
Notice!
If the fire panel automatically switches to night mode during an
ongoing verification time, an alarm is triggered immediately.
Notice!
If during the verification time in one zone an alarm is triggered
in another zone, which is programmed as alarm verification, an
alarm is triggered immediately.
If a zone programmed as alarm verification detects an alarm, it
triggers an alarm, which is delayed.