en | Operation
Testing the zones
NOTICE!
The fire panel features a test memory, which stores all the
panel's testing procedures. All memory entries are assigned a
date and time stamp and cannot be deleted.
The test memory can be called in operating levels 1 and 2.
Use a manufacturer-approved test device to test each individual
detector in the zones currently in test mode. In each case, use
the test device to trigger an alarm.
NOTICE!
The fire panel test function is designed for operation by a single
person:
The fire panel automatically resets the alarm 15 seconds after
an alarm is triggered in a zone in test mode. This is followed by
the set time for disabling the zone and the stabilization time for
the detectors. The next detector can then be tested.
Removing individual zones from test mode
Access the Zones menu in test mode as described above. Use
the zone keys to cancel test mode for the relevant zones. The
code below the selected zone in the LCD disappears.
Disabling zones
CAUTION!
Only disable zones for brief periods of time. Disabled zones will
not trigger an alarm in the event of a fire.
Press the "Test" key and then zone key 3.
3
This takes you to the Dis/Enable submenu
Press zone key 1.
1
This takes you to the Zones submenu