Conventional Fire Panel
Select the zones to be disabled. To do so, press the relevant
1
8
...
zone keys (1 to 8).
A code appears below the selected zone(s) in the LCD.
Confirm your selection with the ACK key.
The "Disable" LED and the LEDs for the selected zones are
ACK
illuminated yellow.
Re-enabling zones
Go to the Disable Zones menu as described above. Use the zone
keys to cancel existing disablements. The code below the
selected zone in the LCD disappears.
Disabling notification appliances
Press the "Test" key and then zone key 3.
3
This takes you to the Dis/Enable submenu
Press zone key 2.
2
You are prompted to confirm the disablement.
ACK
RESET
When you disable the notification appliances, a message
confirming the disablement appears on the LCD after exiting
the menu.
Re-enabling notification appliances
Go to the Disable NAC menu as described above. You are
prompted to confirm the re-enablement. Press the ACK key. The
notification appliances are re-enabled.
Disabling relays
Press the "Test" key and then zone key 3.
3
This takes you to the Dis/Enable submenu
Bosch Sicherheitssysteme GmbH
Press the ACK key.
The notification appliances are now disabled.
Press the "Reset" key.
The notification appliances are not disabled.
Operation Guide
Operation | en
F.01U.172.982 | 5.0 | 2012.04
23