Communication Detail Settings - Mitsubishi Electric GOT 1000 Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT 1000:
Table of Contents

Advertisement

2

Communication detail settings

(1) GT16
Item
GOT NET No.
GOT PLC No.
*1
GOT IP Address
Ethernet Download Port
*1
No.
*1
Subnet Mask
*1
Default Gateway
GOT Port No.
(Communication)
Retry
Startup Time
Timeout Time
Delay Time
2 - 8
2.2 Preparatory Procedures for Monitoring
2.2.3 Setting communication interface (Communication settings)
Description
Set the network No. of the GOT.
<Default: 1>
Set the station No. of the GOT.
<Default: 1>
Set the IP address of the GOT.
<Default: 192.168.3.18>
Set the GOT port No. for Ethernet download.
<Default: 5014>
Set the subnet mask for the sub network. (Only for connection via
router)
If the sub network is not used, the default value is set.
<Default: 255.255.255.0>
Set the router address of the default gateway where the GOT is
connected. (Only for communication via router)
<Default: 0.0.0.0>
Set the GOT port No. for the connection with the Ethernet module.
<Default: 5001>
Set the number of retries to be performed when a communication
error occurs.
When receiving no response after retries, the communication
times out.
<Default: 3 Times>
Specify the time period from the GOT startup until GOT starts the
communication with the PLC CPU.
<Default: 3 Sec>
Set the time period for a communication to time out.
<Default: 3 Sec>
Set the delay time for reducing the load of the network/destination
PLC.
<Default: 0ms>
Range
1 to 239
1 to 64
0.0.0.0 to 255.255.255.255
1024 to 5010, 5014 to 65534
(Except for 5011, 5012 and 5013)
0.0.0.0 to 255.255.255.255
0.0.0.0 to 255.255.255.255
1024 to 5010, 5014 to 65534
(Except for 5011, 5012 and 5013)
0 to 5 Times
3 to 255 Sec
3 to 90 Sec
0 to 10000 ( 10 ms)